摘要
通过对一起220 kV母线反充电引起的电压切换装置元件烧毁事件的分析,得出电压切换双位置继电器没有返回导致两条母线二次并列是引起此次事件的直接原因,并提出了相应的防范措施。
Through the analysis of a 220 kV bus reverse charging caused by the voltage switching device component burnout event,it is concluded that the voltage switching double position relay did not return and the two buses are paralleled twice as the direct cause of this event.Corresponding preventive measures.
作者
李纪昌
李颖慧
Li Ji-chang;Li Ying-hui
出处
《电力系统装备》
2021年第24期69-70,共2页
Electric Power System Equipment
关键词
母线反充电
电压切换
防范措施
bus reverse charging
voltage switching
preventive measures