期刊文献+

基于油中甲醇含量的变压器绝缘纸老化状况评估技术研究

Ageing Evaluation Technology of Transformer Insulating Paper Based on Methanol Content in Oil
下载PDF
导出
摘要 通过对绝缘纸老化特征产物甲醇的检测分析,探究甲醇含量与绝缘纸聚合度之间的相关性,提出表征绝缘纸老化状况的油中甲醇含量的特征参考值。结果表明:绝缘纸聚合度的对数与甲醇含量之间存在良好的线性相关性,且在不同实验条件下,其线性关系均高度相似,可表示为lnDP=aC+b。针对不同电压等级变压器提出的表征绝缘纸老化状况的油中甲醇含量特征值,可对绝缘纸老化状况进行有效判断,从而诊断和评估变压器的运行状态。 The correlation between methanol content and polymerization degree of insulating paper was studied through the detection and analysis of ageing characteristic product methanol of insulating paper,and the characteristic parameter of methanol content in oil,which can characterize the ageing state of insulating paper,was put forward.The results show that there is a good linear correlation between the polymerization degree logarithm of insulating paper and the methanol content,and the linear correlations are highly similar under different experimental conditions,which can be expressed as lnDP=aC+b.The characteristic values of methanol content in oil proposed for transformers with different voltage levels can judge the ageing state of insulating paper effectively,and thus the operation status of transformer can be diagnosed and evaluated.
作者 杨雪滢 李宗红 周嘉璐 宋玉锋 程雪婷 YANG Xueying;LI Zonghong;ZHOU Jialu;SONG Yufeng;CHENG Xueting(Yunnan Electric Power Research Institute of China Southern Power Grid,Kunming 650217,China;Pu'er Power Supply Bureau of China Southern Power Grid,Pu'er 665000,China)
出处 《绝缘材料》 CAS 北大核心 2022年第1期67-72,共6页 Insulating Materials
基金 云南电网有限责任公司科技项目(YNKJXM20190707)。
关键词 绝缘纸 老化 甲醇 insulating paper ageing methanol
  • 相关文献

参考文献3

二级参考文献38

  • 1陈嘉川,谢益民,李彦春,等.大然高分子科学[M].北京:科学出版社,2008.
  • 2CHEN J C, XIE Y M, LI Y C, et. al, Natural Polymer Science [ M ]. Beijing : Science Press Ltd., 2008.
  • 3ZOU X J, GURNAGUL N,UESAKA T.Accelerated aging of papers of pure cellulose : mechanism of cellulose deg- radation and paper embrittlement [ J ] .Polymer Degrada- tion and Stability, 1994,43(3) :393-402.
  • 4LUNDGAARD L E, HANSEN W, LINHJELL D.Aging of oil impregnated paper in power transformers [ J ]. IEEE Transactions on Power Delivery, 2004,19 ( 1 ) : 230-239.
  • 5DING H Z, WANG Z D.Time-temperature superposition method for predicting the permanence of paper by ex- trapolating accelerated ageing data to ambient condi- tions[ J] .Cellulose ,2007,14(3) : 171-181.
  • 6KOLAR J.Mechanism of autoxidatare degradation of cel-lulse [ J ]. Restaurator, 1997,18 (4) : 163-176.
  • 7GLOMMESE M H, LILAND K B, LUNDGAARD L E. Oxidation of Paper Insulation in Transformers[ J ] .IEEE Transactions on Dielectrics and Electrical Insulation, 2010,17 ( 3 ) : 939-946.
  • 8ROBERT R, BARBATI S, RICQ N, et al. Intermediates in wet oxidation of cellulose : identification of hydroxyl radical and characterization of hydrogen peroxide [ J l- Water Research, 2002,36 ( 19 ) : 4 821-4 829.
  • 9LUNDGAARD L E, HANSEN W, LINHJELL D, et al. Aging of oil-impregnated paper in power transformers[J]. IEEE Transactions on Power Delivery, 2004, 19 ( 1 ) : 230-239.
  • 10LILAND K B, KES M, ESE M H G, et al.Study of oxi- dation and hydrolysis of oil Impregnated paper insula- tion for transformers using a microcalorimeter[ J ] .IEEE Transactions on Dielectrics and Electrical Insulation, 2011,18(6) :2 059-2 068.

共引文献13