期刊文献+

迪拜某电站竖井式地下厂房衬砌结构设计

Lining structure design of shaft type underground powerhouse of a power station in Dubai
下载PDF
导出
摘要 迪拜某抽水蓄能电站拟采用竖井式地下厂房,厂房竖井设计高度为70.5 m,净直径约为44.0 m。由于厂房距离下水库较近,外水压力须按全水头并考虑1.35倍的荷载分项系数,运行期厂房衬砌将承受巨大的外水压力,对衬砌结构的安全非常不利。文中设计了多种衬砌结构型式,采用ABAQUS软件进行线性及非线性计算方法进行验证并优化,最终提出了经济合理的衬砌结构型式。该衬砌结构满足安全稳定性要求,降低了工程投资,其研究方法和计算结论可供类似工程参考。 A pumped storage power station in Dubai plans to adopt a shaft type underground powerhouse, with a shaft design height of 70.5 m and a net diameter of about 44.0 m. As the powerhouse is close to the lower reservoir, the external water pressure should be based on the full water head and 1.35 times of the sub-load coefficient should be considered. During the operation period,the lining of the workshop will bear huge external water pressure, which is very detrimental to the safety of the lining structure. In this paper, a variety of lining structures are designed, and ABAQUS software is used to verify and optimize the linear and nonlinear calculation methods. Finally, an economic and reasonable lining structure is proposed. The lining structure meets the requirement of safety and stability and reduces the project investment. The research method and calculation conclusion can be used as reference for similar projects.
作者 熊平华 林小芳 XIONG Ping-hua;LIN Xiao-fang
出处 《东北水利水电》 2022年第2期1-3,13,71,共5页 Water Resources & Hydropower of Northeast China
关键词 竖井式地下厂房 衬砌 非线性计算 ABAQUS 抽水蓄能电站 迪拜 shaft type underground powerhouse lining nonlinear calculation ABAQUS pumped storage power station Dubai
  • 相关文献

参考文献4

二级参考文献5

  • 1[2]ABAQUS Analysis User's Manual,ABAQUS,Inc,2006
  • 2[4]ABAQUS Theory Manual,ABAQUS,Inc,2006
  • 3ABAQUS Theory Manual,ABAQUS,Inc,2003.
  • 4.DL/T 5141-2001,水电站压力钢管设计规范[S].北京:中国电力出版社,2002..
  • 5伏义淑,吴汉明,杨学堂,杨耀,熊德炎,龚国芝.三峡电站压力管道结构模型制作及试验研究[J].武汉水利电力大学(宜昌)学报,1998,20(1):12-18. 被引量:10

共引文献53

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部