期刊文献+

一起110 kV变压器套管发热缺陷分析及处理 被引量:6

Analysis and Treatment on a Heating Fault of 110 kV Transformer Bushing
下载PDF
导出
摘要 通过红外测温发现一起110 kV变压器套管将军帽发热故障,介绍故障检查处理过程,并分析故障原因。分析结果表明斜圈弹簧缺失是导致本次故障的直接原因,整改后变压器运行效果良好。最后,针对此类故障的分析与处理提出建议。 In this paper,a heating fault of 110 kV transformer bushing is found through infrared temperature measurement.The process of fault inspection and treatment is introduced,and the reason of the heating fault is analyzed.The analysis result shows that the missing of inclined coil spring is the direct cause of this fault,and transformer operates normally after rectification.Finally,suggestions are put forward for analysis and treatment of such faults.
作者 庄先涛 郝为 种俊龙 ZHUANG Xiantao;HAO Wei;CHONG Junlong(State Grid Suining Power Supply Company,Suining 629000,China)
出处 《湖南电力》 2022年第1期103-106,共4页 Hunan Electric Power
关键词 变压器套管 红外测温 发热缺陷 故障分析 transformer bushing infrared temperature measurement heating fault fault analysis
  • 相关文献

参考文献15

二级参考文献107

共引文献286

同被引文献82

引证文献6

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部