摘要
Principal component analysis(PCA)has been already employed for fault detection of air conditioning systems.The sliding window,which is composed of some parameters satisfying with thermal load balance,can select the target historical fault-free reference data as the template which is similar to the current snapshot data.The size of sliding window is usually given according to empirical values,while the influence of different sizes of sliding windows on fault detection of an air conditioning system is not further studied.The air conditioning system is a dynamic response process,and the operating parameters change with the change of the load,while the response of the controller is delayed.In a variable air volume(VAV)air conditioning system controlled by the total air volume method,in order to ensure sufficient response time,30 data points are selected first,and then their multiples are selected.Three different sizes of sliding windows with 30,60 and 90 data points are applied to compare the fault detection effect in this paper.The results show that if the size of the sliding window is 60 data points,the average fault-free detection ratio is 80.17%in fault-free testing days,and the average fault detection ratio is 88.47%in faulty testing days.
作者
YANG Xuebin
MA Yanyun
HE Ruru
WANG Ji
LUO Wenjun
杨学宾;马艳云;何如如;王吉;罗雯军(College of Environmental Science and Engineering,Donghua University,Shanghai 201620,China;Shanghai Division,China Ship Development and Design Center,Shanghai 201108,China)
基金
Fundamental Research Funds for the Central Universities of Ministry of Education of China。