摘要
文章介绍了一起某电厂主变压器倒挂运行时,电压互感器发生分频谐振,导致主变压器低压侧开口三角电压报警动作的案例。结合现场检查处理情况,对铁磁谐振的原理进行了分析,并根据现场实际情况提出了变更运行方式、装设消谐电阻及消谐装置等应对措施。
This paper introduces a case of voltage transformer frequency division resonance occurring when the main transformer is running upside down in a hydropower plant,which leads to the voltage alarm of the open-delta connection in main transformer lowvoltage side.The principle of ferromagnetic resonance is analyzed in combination with the on-site inspection and treatment,some countermeasures are put forward according to the actual situation,such as changing the operation mode,installing the harmonic elimination resistor and the harmonic elimination device.
作者
王权
李炜
WANG Quan;LI Wei(Gezhouba Hydropower Plant,Yichang,443002,China)
出处
《水电与抽水蓄能》
2022年第1期35-39,共5页
Hydropower and Pumped Storage
关键词
主变压器倒挂
分频谐振
过电压
main transformer inverted operation
frequency division resonance
overvoltage