期刊文献+

太阳能驱动的中空纤维膜液体除湿系统[火用]分析

EXERGY ANALYSIS OF SOLAR POWERED HOLLOW FIBER MEMBRANE LIQUID DEHUMIDIFICATION SYSTEM
下载PDF
导出
摘要 建立太阳能驱动的中空纤维膜液体除湿系统的[火用]分析模型,对系统各部件进行[火用]分析,分析空气、冷水进口参数和溶液流量对系统性能的影响。结果显示:1)影响系统[火用]效率较大的因素是空气进口含湿量、空气流量、冷水温度和冷水流量;2)整个系统中太阳能集热器部件的[火用]损最大,可见提高太阳能集热器的性能是提高系统[火用]效率的关键。 Solar powered hollow fiber membrane liquid dehumidification system is an efficient,energy-saving,renewable and non-contact dehumidification system,which can effectively solve carry-over problem of traditional liquid dehumidification. In the present work,an exergy analysis model of solar powered hollow fiber membrane liquid dehumidification system is developed. The exergy of the component is analyzed. Effect of inlet paraments of air and cold-water,and solution flow rate on the system performance is investigated.The results show that the major factors affecting exergy efficiency of system are inlet air humidity,flow rate of inlet air,temperature of cold-water,and flow rate of cold-water. In the whole system,the biggest part of exergy destruction happens in solar collector. Improving the solar collector performance is the key way to improve the system exergy efficiency.
作者 门玉葵 李南风 何智鹏 梁才航 李振兴 童晓漫 Men Yukui;Li Nanfeng;He Zhipeng;Liang Caihang;Li Zhenxing;Tong Xiaoman(School of Mechanical&Electrical Engineering,Guilin University of Electronic Technology,Guilin 541004,China;School of energy and Building Environment,Guilin University of Aerospace Technology,Guilin 541004,China;College of Environmental&Resource Sciences,Shanxi University,Taiyuan 030006,China)
出处 《太阳能学报》 EI CAS CSCD 北大核心 2022年第2期261-267,共7页 Acta Energiae Solaris Sinica
基金 国家自然科学基金(51566002) 广西自然科学基金(2018GXNSFAA281347) 广西制造系统与先进技术重点实验室基金(19050-44-001Z) 山西自然科学基金(201701D121020)。
关键词 太阳能 空气调节 太阳能集热器 液体除湿 中空纤维膜 solar energy exergy air conditioning humidity control liquid desiccant hollow fiber membrane
  • 相关文献

参考文献4

二级参考文献39

  • 1刘晓华,江亿,曲凯阳,陈晓阳.叉流除湿器中溶液与空气热质交换模型[J].暖通空调,2005,35(1):115-119. 被引量:27
  • 2殷勇高,张小松,蒋毅.基于溶液除湿潜能释能的制冷系统的构建与研究[J].制冷学报,2006,27(5):26-30. 被引量:6
  • 3施明恒,杜斌,赵云.太阳能液体除湿空调系统再生和蓄能特性的研究[J].太阳能学报,2006,27(1):49-54. 被引量:20
  • 4Bergero S,Chiari A. Experimental and theoretical analysis of air humidification/dehumidification processes using hydrophobic capillary contactors[J].{H}Applied Tnermal Engineering,2001.1119-1135.
  • 5Kneifel K,Nowak S,Albrecht W. Hollow fiber membrane contactor for air humidity control[J].{H}Journal of Membrane Science,2006.241-251.
  • 6Zhang L Z,Huang S M,Pei L X. Conjugate heat and mass transfer in a cross-flow hollow fiber membrane contactor for liquid desiccant air dehumidification[J].Int J Heat Mass Transf,2012.8061-8072.
  • 7Huang S M,Zhang L Z,Tang K,Pei L X. Turbulent heat and mass transfer across a hollow fiber membrane tube bank in liquid desiccant air dehumidification[J].ASME J Heat Transf,2012.82001-821-8.
  • 8Zhang L Z,Huang S M,Chi J H,Pei L X. Conjugate heat and mass transfer in a hollow fiber membrane module for liquid desiccant air dehumidification:a free surface model approach[J].Int J Heat Mass Transf,2012.3789-3799.
  • 9Huang S M,Zhang L Z,Pei L X. Transport phenomena in a cross-flow hollow fiber membrane bundle used for liquid desiccant air dehumidification[J].Indoor Built Enviro,2013.
  • 10Kneifel K,Nowak S,Albrecht W. Hollow fiber membrane contactor for air humidity control[J].{H}Journal of Membrane Science,2006.241-251.

共引文献15