摘要
在华东地区某数据中心中,为了确保水冷空调系统中蓄冷罐的功能、评估不同负载下蓄冷罐独立供冷的持续时间,通过开展蓄冷罐在不同工况下的充放冷测试,分别得出蓄冷罐的放冷持续时间和充冷所需时长,在此基础上,对测试数据进一步分析,得出蓄冷罐作为后备冷源切实有效的结论。
In a data center in east China,in order to ensure the function of water-cooled air conditioning system in the storage tank under different load,evaluate the duration of the cold storage tank independent cooling,by conducting the cold storage tank under different working conditions was released and complementary tests,the cold storage tank is calculated release duration and cold added the required amount of time,on this basis,further analysis of test data,It is concluded that the storage tank is effective as the backup cold source.