摘要
气体绝缘金属封闭输电线路(gas insulated metal-enclosed transmission line,GIL)中绝缘气体热学特性会影响GIL整体绝缘性能。目前,国内外对C_(4)F_(7)N/CO_(2)混合新型环保气体应用于GIL的研究刚刚起步,其热学特性尚不明确。为此对特高压C_(4)F_(7)N/CO_(2)混合气体GIL建立了温度-流体多物理场仿真模型,通过开展现场温升试验对该模型进行了有效性验证,研究了额定电流下GIL内部温度场分布及内部气体密度场、流速场分布,以及不同通流水平下导体和铝合金外壳顶部温升关系,并对比分析了在C_(4)F_(7)N/CO_(2)与SF;两种不同气体下GIL内部温升的差异性。研究结果表明:C_(4)F_(7)N/CO_(2)气体GIL内部温度梯度整体大于SF;气体GIL,在后续环保型GIL设计中应关注这一问题;相同通流条件下C_(4)F_(7)N/CO_(2)气体GIL与SF;气体GIL温度分布差异的主要原因为SF;对流性能优于C_(4)F_(7)N/CO_(2)混合气体;探索了C_(4)F_(7)N/CO_(2)GIL外壳顶部温升与GIL中心导体温升间的关系,GIL导–壳温升比例系数为0.482,该系数可应用于后续基于外壳温度的中心导体温度监测系统中。
The thermal properties of the insulating gas in a gas insulated metal-enclosed transmission line(GIL)will affect the overall insulation performance of the GIL.At present,domestic and foreign research on the application of C_(4)F_(7)N/CO_(2) mixed environmentally friendly gas to GIL has just started,and its thermal characteristics are still unclear.Therefore,we established a temperature-fluid multi-physical field coupling simulation model for the environment-friendly UHV C_(4)F_(7)N/CO_(2) mixed gas GIL and conducted simulation research.An on-site temperature rise test to effectively verify the model was also conducted.The research results indicate that the internal temperature gradient of environmental-friendly GIL is larger than that of SF;GIL,which should be paid attention to in the subsequent design of environmental-friendly GIL.The convection performance of SF;is better than that of C_(4)F_(7)N/CO_(2) mixed gas,which will cause differences of temperature distribution in GIL.The relationship between the temperature rise of GIL center conductor and the top of the C_(4)F_(7)N/CO_(2) GIL shell is explored,and the GIL conductor-case temperature rise response coefficient is defined.This coefficient can be applied to the subsequent center conductor temperature monitoring system based on the shell temperature.
作者
史荣斌
秦炜淇
张猛
周宏扬
王浩
叶三排
马国明
SHI Rongbin;QIN Weiqi;ZHANG Meng;ZHOU Hongyang;WANG Hao;YE Sanpai;MA Guoming(State Key Laboratory of Alternate Electrical Power System with Renewable Energy Sources,North China Electric Power University,Beijing 102206,China;China Electric Power Research Institute,Beijing 100192,China;Pinggao Group Co.,Ltd.,Pingdingshan 467000,China)
出处
《高电压技术》
EI
CAS
CSCD
北大核心
2022年第2期698-705,共8页
High Voltage Engineering
基金
国家重点研发计划(2017YFB0903800)。