摘要
提出一种4-SiC混合三电平有源中点钳位逆变器(three-level active neutral point clamped,3L-ANPC)及其损耗均衡调制策略,将硬开关损耗分配给不同SiC MOSFET,让通态损耗高的SiCMOSFET仅承受关断损耗,而通态损耗低的SiCMOSFET仅承受开通损耗;并提出将续流状态2条电流支路并联,降低续流状态的通态损耗。分析所提新4-SiC混合3L-ANPC的工作原理和模态,理论计算和对比传统4-SiC和所提4-SiC混合方案的损耗。最后,搭建一台2kW的单相3L-ANPC逆变器样机,验证所提4-SiC混合方案相比与传统4-SiC混合方案,优化了SiC器件损耗均衡,并提高了变换效率。
A 4-SiC hybrid three-level active neutral point clamped(3L-ANPC) inverter and dedicate modulation scheme with the loss balance distribution characteristic were proposed.The turn-on switching loss was distributed to the SiC MOSFET with a lower conduction loss. Moreover, the turn-off switching loss was distributed to the SiC MOSFET with a higher conduction loss. In addition, dual freewheeling paths were used to lower the conduction losses during freewheeling modes.Both the operation principle and working states were analyzed in detail. The calculated power losses of the proposed new 4-SiC hybrid 3L-ANPC inverter and the conventional 4-SiC hybrid 3L-ANPC inverter were addressed and compared.Finally, a 2kW prototype was built. Experimental results and analysis show that compared with the conventional 4-SiC hybrid 3L-ANPC inverter, the proposed 4-SiC 3L-ANPC inverter and dedicate modulation scheme exhibit higher efficiency and better loss balance performance.
作者
娄修弢
张犁
陈永炜
沈竹
郑仲舒
LOU Xiutao;ZHANG Li;CHEN Yongwei;SHEN Zhu;ZHENG Zhongshu(College of Energy and Electrical Engineering,Hohai University,Nanjing 211100,Jiangsu Province,China;State Grid Zhejiang Electric Power Co.,Ltd.,Huzhou Power Supply Company,Huzhou 313000,Zhejiang Province,China)
出处
《中国电机工程学报》
EI
CSCD
北大核心
2022年第5期1925-1932,共8页
Proceedings of the CSEE
基金
国家电网浙江省电力公司科技项目(2019-HUZJTKJ-14)
江苏省六大人才高峰创新团队(2019-TD-XNY-001)
中央高校基本科研业务费专项资金(B210203030)。