摘要 近年来国内输配电线路引发森林草原火灾风险越来越高。为探究低压架空裸导线引发火灾的特性和机理,本文搭建了380/220 V低压架空裸导线模拟实验平台,开展了树枝短接线路实验、两相线路相间接触短路实验,并对线路穿越林区与树木接近处经常出现短路熔痕的现象进行了实验和仿真分析。结果表明:正常树枝和雨水浸湿后的树枝短接线路,不会发生放电打火现象,也无温升和泄漏电流产生。两相线路相间接触短路,放电产生的喷溅熔珠掉落至地面温度较低,不足以引燃地面的可燃物。结合近年低压线路火灾原因调查结果分析,线路过流保护开关对低压线路引发的火灾有显著预防作用。线路穿越林区与树木接近处的短路熔痕,可能为大风大雨天气下树枝短接线路放电产生。所做研究可为低压线路火灾原因调查和防范提供技术参考。 In recent years, the risk of fire in forest grassland caused by power transmission and distribution lines in China is increasing. In order to explore the characteristics and mechanism of low-voltage overhead bare wire fire, a 380/220 V lowvoltage line simulation experiment platform was built. Branches short-circuiting lines and two phase contact short circuit tests were carried out. The phenomenon of short-circuited melted marks often occurred in the close place between low voltage bare wire crossing forest area and trees was analyzed by the experiments and simulation. The results indicate that there were no spark discharges when normal twig and rain-soaked twig overlapped line. The temperature of the splash beads generated by the contact short-circuit discharge between two phase lines falling to the ground is low, which can not ignite the combustible material on the ground. Combined with the investigation results of low-voltage line fire causes in recent years, the line overcurrent protection plays a significant role in preventing lowvoltage line fire. In strong wind and heavy rain, the twigs and leaves short-circuit two phase line, which may lead to short-circuit discharge and obvious melted marks on the wire. The research can provide technical reference for low-voltage line fire cause investigation and prevention.
作者 李劲松 刘文昊 杨冬冬 俞华 LI Jin-song;LIU Wen-hao;YANG Dong-dong;YU Hua(State Grid Shanxi Electric Power Research Institute,Shanxi Taiyuan 030001,China;State Grid Maintenance Co.,of SEPC,Beijing 102488,China)
出处 《消防科学与技术》 CAS 北大核心 2022年第4期546-550,共5页 Fire Science and Technology
基金 国网山西省电力公司科技项目“高压电缆绝缘状态评估与差异化防(灭)火技术研究”(52053020000V)。
关键词 低压架空线路 森林火灾 裸导线 火灾调查 输配电线路火灾 low-voltage overhead power lines forest fire bare wire fire investigation transmission and distribution line fire
  • 相关文献

参考文献11

二级参考文献150

共引文献271

同被引文献36

引证文献2

二级引证文献11

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部