摘要
某核电厂6 kV循环水泵机械部分在做定期维护时,因两点接地产生环流,就地电动机保护装置和主控室报警系统误发“循环水泵电机接地”报警。对上述误报警的原因进行了分析并提出解决方案,对今后解决接地环流的问题提供了方向。
When the mechanical part of 6 kV circulating water pump in a nuclear power plant was under regular maintenance,the circulating current was generated due to two-point grounding,and the local motor protection device and the alarm system in the main control room mistakenly sent the alarm of"circulating water pump motor grounding".The causes of the above false alarm are analyzed and the solutions are put forward,which provides a direction for solving the problem of grounding circulation in the future.
作者
孙玉朋
蒋军
刘争光
吴建超
SUN Yupeng;JIANG Jun;LIU Zhengguang;WU Jianchao(China Nuclear Power Operation and Management Co.,Ltd.,Haiyan 314300,China;Chengdu Haiguang Nuclear Power Technology Service Co.,Ltd.,Chengdu 610000,China)
出处
《电工技术》
2022年第7期156-158,共3页
Electric Engineering
关键词
接地
误报警
改进
grounding
false alarm
improvement