期刊文献+

市电油机切换间隔UPS电池充放电性能分析

Analysis of Charging and Discharging Performance of UPS Battery at Switching Interval between Mains and Generator
下载PDF
导出
摘要 从一起通信大楼高压线路年度例行检修测试时出现的市电油机切换操作引起UPS输出掉电故障案例着手,分析市电油机切换操作中UPS电池充放电性能,提出了市电油机切换的时间间隔高于30 min的要求,对保障通信大楼安全、可靠、稳定供电具有重要作用。 Starting from a case of UPS output power failure caused by the switching operation of the mains oil generator during the annual routine maintenance test of the high-voltage line of the communication building,the charging and discharging performance of the UPS battery during the mains oil generator switching operation is analyzed,and the mains oil generator switching operation is proposed.The time interval is higher than the requirement of 30 minutes,which plays an important role in ensuring the safe,reliable and stable power supply of the communication building.
作者 张维东 ZHANG Weidong(China Telecom Chongqing Network Monitoring and Maintenance Center,Chongqing 400042,China)
出处 《通信电源技术》 2021年第24期153-155,共3页 Telecom Power Technology
关键词 电池充放电 切换间隔 性能分析 battery charge and discharge switching interval performance analysis
  • 相关文献

参考文献3

二级参考文献14

共引文献10

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部