摘要
针对一起500 kV油浸式电流互感器爆炸事故展开调查,通过诊断试验和解体分析综合研判本次事故的主要原因为该电流互感器绝缘水平偏低,在长期运行过程中绝缘随之劣化,随着时间发展造成主绝缘击穿。对该事故提出相应的应对措施,为同类型电流互感器的故障诊断和运行维护提供参考。
An investigation is done on an explosion accident of 500 kV oil-immersed current transformer.Through diagnostic test and disassembly analysis,it was comprehensively determined that the main cause of the accident was that the insulation level of the current transformer was too low,the insulation deteriorates during long-term operation and comes to the breakdown of the main insulation by time.The corresponding measures are put forward for the accident,which offers reference for fault diagnosis,operation and maintenance of such current transformers.
作者
徐鹏
付文波
盛智蕾
陈昊
谭风雷
张海华
XU Peng;FU Wenbo;SHENG Zhilei;CHEN Hao;TAN Fenglei;ZHANG Haihua(Maintenance Company of State Grid Jiangsu Electric Power Co.,Ltd.,Nanjing 211102)
出处
《电力安全技术》
2022年第4期33-36,共4页
Electric Safety Technology
关键词
油浸式电流互感器
故障成因
解体分析
主绝缘击穿
oil-immersed current transformer
cause of fault
disassembly analysis
breakdown of main insulation