武汉某数据中心空调系统设计及节能分析 被引量:5

Air conditioning system design and energy saving analysis of a data center in Wuhan
下载PDF
导出
摘要 分析了武汉地区自然冷却资源量,介绍了数据中心常规系统流程的运行逻辑,结合完全自然冷却在时间轴上呈碎片化分布的特性,指出其利用自然冷却效率较低的原因。为提高数据中心能源利用效率,该项目采用蓄冷罐释冷混水技术,通过对空调系统进行详细分析,采用了一种新型混水温控阀,达到快速混水的目的。IT设备在满负荷条件下,PUE为1.336,满足设计要求,节能效果显著。 This paper analyses the amount of free cooling resources in Wuhan,and presents the operating logic of the conventional system process of the data center.Combined with the fragmented distribution of complete free cooling on the time axis,this paper points out the reasons for its low efficiency in using free cooling.In order to improve the energy efficiency of the data center,this project adopts the water mixing technology with cold storage tank to release cold.The air conditioning system is analysed in detail,and a new type of water mixing temperature control valve is adopted to achieve the purpose of rapid water mixing.Under full load conditions of IT equipment,the data center has a PUE of 1.336,which meets the design requirements and has significant energy-saving effects.
作者 唐瑞 熊汉兵 杨艳 刘天宇 李东阳 Tang Rui;Xiong Hanbing;Yang Yan;Liu Tianyu;Li Dongyang(Changjiang Institute of Survey,Planning,Design and Research Co.,Ltd.,Wuhan;Wuhan Tengyun Shuleng Technology Co.,Ltd.,Wuhan)
出处 《暖通空调》 2022年第5期96-101,35,共7页 Heating Ventilating & Air Conditioning
关键词 数据中心 空调系统 自然冷却 水蓄冷 电能利用效率 混水阀 data center air conditioning system free cooling water cool storage power usage effectiveness water mixing valve
  • 相关文献

参考文献4

二级参考文献92

  • 1刘道平.蓄冷技术及其应用现状[J].暖通空调,1995,25(4):30-33. 被引量:16
  • 2李竞,吴喜平.蓄冷蓄热技术[J].上海节能,2005(4):78-82. 被引量:14
  • 3郑钢,宋吉.冷却塔供冷系统设计中应该注意的问题[J].制冷与空调,2006,6(2):75-78. 被引量:29
  • 4于航,邓育涌,孙斌,张旭,林建海,孙禾,贺春丽.温度分层型水蓄冷罐的仿真研究[J].能源技术,2006,27(3):120-122. 被引量:20
  • 5Sharma R K, Bash C E, Patel C D. Dimensionless parameters for evaluation of thermal design and performance of large scale data centers [C]// Proceedings of the American Institute of Aeronautics and Astronautics (AIAA), St. Louis, MO, 2002, Paper AIAA- 2002- 3091.
  • 6Bash C E, Patel C D, Sharma R K. Efficient thermal management of data centers immediate and long term research needs [J]. Int. J. Heating, Ventilating, Air Conditioning and Refrigeration Research, 2003, 9 (2) : 137- 152.
  • 7Magunus K. Herrlin. Airflow and Cooling Performance of Data Centers: Two Performance Metrics [J]. ASHRAE Transactions, 2008, 114 (2) : 182-187.
  • 8TC 9.9 - Mission Critical Facilities, 2005. Thermal Guidelines for Data Processing Environments. ASHRAE.
  • 9GB 50174-2008电子信息系统机焐设计规范[S].北京:中_计划出版社,2009.
  • 10GB 50174-xxxx数据中心设计规范(送审稿)[S].北京:中闺计划出版社,2014.

共引文献101

同被引文献55

引证文献5

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部