750 kV GIS盆式绝缘子开裂导致漏气分析与治理 被引量:1

Analysis and Treatment of Air Leakage Caused by Cracking of 750 kV GIS Basin Insulator
下载PDF
导出
摘要 针对两起气体绝缘金属开关设备(GIS)因盆式绝缘子开裂导致的设备漏气问题,对发生故障的盆式绝缘子进行了现场拆解,并通过对开裂盆子的受力分析和ANSYS仿真分析,判定了盆式绝缘子开裂的原因,最后对盆式绝缘子的结构进行了改进。经工程运行验证,改进后绝缘盆子处运行效果良好。 In view of two gas insulated switchgear(GIS) cases of air leakage caused by cracking of basin insulators, the faulty basin insulators were disassembled on site, and the cracking reason was determined by force analysis of cracked basin and ANSYS simulation analysis. Finally, the structure of the basin insulator is improved, which has been verified by the project operation. After the improvement, the operation effect is good.
作者 戴立庆 王巧燕 徐铁胜 林恒青 DAI Liqing;WANG Qiaoyan;XU Tiesheng;LIN Hengqing(Machinery and Intelligent Manufacturing College,Fujian Chuanzheng Communications College,Fuzhou 350007,China;Fuzhou Power Supply Company of State Grid Fujian Electric Power Co.Ltd.,Fuzhou 350004,China;Inspection and Repair Branch of State Grid Qinghai Power Co.Ltd.,Xining 810003,China)
出处 《新乡学院学报》 2022年第6期56-58,共3页 Journal of Xinxiang University
关键词 气体绝缘金属开关设备 盆式绝缘子 有限元 裂纹 gas insulated switchgear basin type insulator finite element crack