期刊文献+

预制化并机UPS系统不均流问题的研究

Research on Current Imbalance of Prefabricated Parallel UPS System
下载PDF
导出
摘要 随着数据中心日益增长的敏捷交付和高效运营要求,越来越多的预制化产品在现场落地。作为IT设备供电关键的不间断电源(Uninterruptible Power System,UPS)也出现了预制化并机系统的产品。以一例预制化新产品中出现静态旁路带载不均流问题进行分析,结合MATLAB对理论进行分析并提出改善措施。实际测试结果验证了仿真数据的有效性。 With the increasing requirements for the agile delivery and efficient operation of the data center,more and more prefabricated products are landing on the site.As the key equipment for power supply of IT equipment,Uninterruptible Power System(UPS)also has products of prefabricated parallel system.This paper analyzes the problem of uneven flow of static bypass load in a prefabricated new product,analyzes the theory combined with MATLAB,and puts forward improvement measures.The actual test results verify the effectiveness of the simulation data.
作者 滑祥 张锐 HUA Xiang;ZHANG Rui(GDS Holdings Limited.,Shanghai 200131,China)
出处 《通信电源技术》 2022年第3期15-17,21,共4页 Telecom Power Technology
关键词 不间断电源(UPS) 静态旁路 带载不均流 预制化并机系统 Uninterruptible Power System(UPS) static bypass current imbalance prefabricated parallel system