摘要
全钒液流电池在运行时会产生氢气,为了保证人员及设备的安全,提出了预防性事故通风系统,设计了两个通风方案。方案一是在储罐层和电堆层分别设置独立的预防性事故通风系统;方案二是在两层之间的楼板上设置大量格栅,使上下贯通成为一个大空间,设置一套预防性事故通风系统。结果表明:方案二更安全可靠,通风效果更好。
In order to ensure the safety of personnel and equipment,apreventive accident ventilation system is proposed,and two ventilation schemes are designed.Scheme one is to set up independent preventive accident ventilation systems in the storage tank layer and the stack layer.Scheme two is to set a large number of grids on the floor slab between the two floors to make the upper and lower through into a large space,and set up a set of preventive accident ventilation system.The results show that scheme two is safer and more reliable,and the ventilation effect is better.
作者
石敏杰
吕浩
岳奕彤
董蕾
SHI Minjie;LYV Hao;YUE Yitong;DONG Lei(Dalian City Thermoelectric Group Company Limited,Dalian 116032,China;Air Force Aviation University,Changchun 130021,China;Northeast Electric Power Design Institute Company Limited of China Power Engineering Consulting Group,Changchun 130021,China)
出处
《吉林电力》
2022年第2期43-46,共4页
Jilin Electric Power
关键词
全钒液流电池
储能车间
通风
氢气
vanadium redox flow battery
energy storage workshops
ventilation
hydrogen