摘要
通过搭建参数可调的重复脉冲法通用实验平台,针对真实的发电电动机转子绕组进行测试,对转子绕组的脉冲传递特性、重复脉冲法的诊断效果和适用性进行分析。试验结果表明,通过提高激励脉冲幅值使诊断灵敏度得到保证后,重复脉冲法可以应用于发电电动机等长绕组转子的匝间短路故障诊断。
A general testing platform of repeated pulse method with adjustable parameters was built to test the rotor winding of a real generator-motor,and the pulse-transferring characteristics of the rotor winding,diagnosing effect and applicability of the repeated pulse method were analyzed.The testing results show that the repeated pulse method can be applied to the fault diagnosing of inter-turn short circuit of long rotor windings like generator-motor after the diagnostic sensitivity is guaranteed by increasing the amplitude of exciting pulse.
作者
张利
孙士涛
王晓军
张婷
邵卫超
张杰
雷雨
刘柏延
ZHANG Li;SUN Shitao;WANG Xiaojun;ZHANG Ting;SHAO Weichao;ZHANG Jie;LEI Yu;LIU Boyan(State Grid Xinyuan Holdings Co.Ltd.,Beijing Shisanling Storage Power Plant,Beijing 100037,China;North China Electric Power Research Institute Co.Ltd.,Beijing 100045,China)
出处
《水电与抽水蓄能》
2022年第3期115-120,共6页
Hydropower and Pumped Storage
关键词
发电电动机
重复脉冲法
灵敏度
generator-motor
repeated pulse method