期刊文献+

冷却塔机房噪声测量及物理封堵降噪效果评估

Acoustic measurement and noise reducing effect evaluation of physical blocking measures for cooling tower plant
下载PDF
导出
摘要 对冷却塔机房噪声源进行声学分析,并基于声学分析的结果,以数个敏感点的声压值为考核指标对机房进行整体降噪处理。在对机房进行缝隙封堵、增设降噪片后,取得了符合设计要求的降噪效果。结果表明,噪声敏感点的声压值由85 dB(A)降低到53 dB(A)。 This paper provided a study on the noise analysis for cooling tower station by acoustic analysis.Based on acoustic analysis results,a whole noise reduction process is carried out for the station and the sound pressure value of several sensitive points is taken as the evaluation indies.Using the gap sealing,adding noise reduction film,the noise level was reduced to an achievable level as design requirement.Testing results showed that the sound pressure of the noise sensitive point decreases from 85 dB(A)to 53 dB(A).
作者 郭彦玲 田沛灵 唐川宇 聂志琪 廖云丹 Guo Yanling;Tian Peiling;Tang Chuanyu;Nie Zhiqi;Liao Yundan(Guangdong Planning and Designing Institute of Telecommunications Co.,LTD,Guangzhou,510006,China;Academy of Building Energy Efficiency of Guangzhou University,School of Civil Engineering,Guangzhou University,Guangzhou 510006,China;Guangdong Provincial Key Laboratory of Building Energy Efficiency and Application Technologies,Guangzhou 510006,China)
出处 《山西建筑》 2022年第14期6-9,14,共5页 Shanxi Architecture
基金 国家自然科学基金青年基金资助项目(编号:51708139)。
关键词 冷却塔 声学分析 噪声控制 降噪措施 cooling tower acoustic analysis noise control noise reduction measures