期刊文献+

某核电站安全厂用水系统奥氏体不锈钢仪表管泄漏原因 被引量:1

Causes of leakage of austenitic stainless steel instrumentation pipe for essential service water system in a nuclear power plant
下载PDF
导出
摘要 某核电站安全厂用水系统奥氏体不锈钢仪表管焊缝处发生泄漏。采用宏观观察、化学成分分析、硬度测试、金相检验和扫描电镜分析,分析了该仪表管泄漏的原因。结果表明:该仪表管内壁焊接热影响区形成严重的回火色,即贫铬氧化层,在海水中氯离子的作用下,管道内壁形成点蚀坑,点蚀坑不断扩展,最终贯穿整个管壁,导致仪表管泄漏。 A leak occurred in the weld of austenitic stainless steel instrumentation pipe for the essential service water system in a nuclear power plant.Macroscopic observation,chemical composition analysis,hardness test,metallographic inspection and scanning electron microscope analysis were used to analyze the reasons for the leakage of the instrumentation pipe.The results showed that the welding heat-affected zone on the inner wall of the instrumentation pipe formed a serious temper color,that was,a chromium-poor oxide layer.Under the action of chloride ions in seawater,pitting pits were formed on the inner wall of the pipe,the pitting pits continued to expand,and finally penetrate the entire pipe wall,causing the instrumentation pipe to leak.
作者 李鸿远 张彦召 张舟永 刘洪群 潘姚凡 LI Hongyuan;ZHANG Yanzhao;ZHANG Zhouyong;LIU Hongqun;PAN Yaofan(CGN Cangnan Nuclear Power Co.,Ltd.,Wenzhou 325000,China;Suzhou Nuclear Power Research Institute,Suzhou 215004,China)
出处 《理化检验(物理分册)》 CAS 2022年第3期45-48,共4页 Physical Testing and Chemical Analysis(Part A:Physical Testing)
关键词 奥氏体不锈钢 泄漏 点蚀 回火色 austenitic stainless steel leakage pitting temper color
  • 相关文献

参考文献9

二级参考文献35

共引文献33

同被引文献15

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部