在一些燃气工程改造项目中,由于现场条件限制、建设时序等因素的影响,存在燃气调压柜与建(构)筑物的水平净距不足、距离道路红线过近等的情况,无法满足规范要求。以3个实际改造项目为例,详细解释了规范条文的具体含义,并结合现场实际给出了可行的技术措施以适当缩小水平净距的要求,可为今后类似工程提供参考。
In some reconstruction projects, due to the influence of site conditions restrictions, construction sequence and other factors, there are some difficulties, such as insufficient horizontal clear distance between the gas regulator and buildings and structures, and close to the road. Taking three actual reconstruction projects as examples, this paper explains the specific meaning of the clauses and restrictions in detail, and gives feasible technical measures to meet the requirements of properly reducing the horizontal clear distance in combination with the actual situation on site, which can provide reference for similar projects in the future.
作者
焦琳
JIAO Lin(Shanghai Gas Engineering Design and Research Co.,Ltd.)
出处
《上海煤气》
2022年第2期8-10,34,共4页
Shanghai Gas
关键词
燃气调压柜
改造工程
设计
实例
gas pressure regulating cabinet
reconstruction project
design
case