期刊文献+

某断路器防跳回路隐患致母线跳闸事故原因分析 被引量:2

Cause Analysis of Bus Tripping Accident Caused by Hidden Danger of Anti Tripping Circuit of a Circuit Breaker
下载PDF
导出
摘要 断路器防跳回路主要由若干继电器及辅助节点组成,继电器之间的配合是保证防跳回路和分、合闸回路正确动作的前提。介绍了某变电站母线跳闸事故,并从各方面进行了全面分析,总结出一种断路器防跳回路隐患,确认该隐患为防跳回路中继电器之间在时间上配合不当,导致母线跳闸事故,提出给出了针对该隐患的解决措施。 The anti-pumping-circuit of circuit breaker is mainly composed of several relays and auxiliary nodes. The cooperation between relays is the premise to ensure the correct action of the anti-pumping-circuit and the opening and closing circuits. This paper introduces a bus trip accident in a substation, and makes a comprehensive analysis from all aspects, summarizes a hidden danger of the anti-pumping-circuit of circuit breaker, and confirms that the hidden danger is that the relay devices of the anti-pumping-circuit do not cooperate properly in time, resulting in the bus trip accident. Finally, the paper gives the solutions to the hidden danger.
作者 童鑫 杨张伟 王雨濛 陶杰 殷忠宁 万欣 TONG Xin;YANG Zhangwei;WANG Yumeng;TAO Jie;YIN Zhongning;WAN Xin(State Grid Anhui Hefei Power Supply Company,Anhui Hefei 230022,China)
出处 《农村电气化》 2022年第8期34-37,共4页 Rural Electrification
关键词 防跳回路 继电器 隐患 跳闸 anti-pumping-circuit relay hidden danger trip