长沙地区某联通机房热管空调改造的节能分析

Energy Saving Analysis of Heat Pipe Air Conditioning Transformation in a Unicom Machine Room in Changsha
下载PDF
导出
摘要 在2030年“碳达峰”及2060年的“碳中和”背景下,各行业纷纷出台各项标准与应用低碳技术以响应国家政策。而IDC(Information Data Center)机房其能耗呈井喷式增长,节能降耗迫在眉睫。针对该形式,日前省发改委出台了“数据中心及5G基站”低碳行动方案。热管自然冷却是降低这一能耗的有效方法之一。针对长沙地区某联通机房热管空调改造项目进行建模分析,并以实测值验证。结果表明,系统的节能率约为38%。是值得在全国范围推广的技术。 Under the background of"carbon peak"in 2030 and"carbon neutralization"in 2060,the form of energy conservation in various industries is severe.The energy consumption of IDC(Information Data Center)room is increasing in a blowout mode,so it is urgent to save energy and reduce consumption.In view of this form,the provincial development and Reform Commission recently issued a low-carbon action plan of"data center and 5 G base station".Natural cooling of heat pipe is one of the effective methods to reduce this energy consumption.This paper analyzes the modeling of a heat pipe air conditioning transformation project in a Unicom room in Changsha,and verifies it with the measured values.The results show that the energy saving rate of the system is about 38%.It is a technology worthy of nationwide promotion.
作者 齐蓉 陈飞虎 杨志新 邢利 廖曙光 Qi Rong;Chen Feihu;Yang Zhixin;Xing Li;Liao Shuguang
出处 《洁净与空调技术》 2022年第3期92-95,共4页 Contamination Control & Air-Conditioning Technology
关键词 碳达峰 碳中和 联通机房 热管空调 节能率 Carbon peak Carbon neutralization Unicom machine room Heat pipe air conditioning Energy saving rate