摘要
为解决隧道二次衬砌裂损整治中面临的净空限制等问题,提出采用超高性能混凝土(UHPC)代替普通混凝土作为衬砌补强材料,并对其可行性及材料力学性能要求进行系统研究。基于异性材料叠合梁理论对裂损衬砌和加固层的共同受力机制进行研究,得到加固材料的力学性能与结构受力特征之间的关系,从而得到加固工程对加固层厚度及UHPC力学性能要求;在此基础上,提出一种实体单元应力和内力换算的计算方法,并通过有限差分法数值模拟,对衬砌与加固材料之间结合面的受力特征进行分析,从而得到加固工程对UHPC和普通混凝土之间黏结强度的要求。研究结果表明:对于承载力损失不超过40%的衬砌,可采用UHPC进行加固;对于承载力损失不超过15%的衬砌,UHPC的使用可将加固层的厚度减小到10 cm左右。
The headroom limit always restricts the crack treatment of tunnel secondary lining.Accordingly,ultra-high-performance concrete(UHPC)is proposed to replace ordinary concrete as a lining reinforcement material,and the feasibility and performance requirements of UHPC application are examined systematically.Based on the composite beam theory of dissimilar materials,the joint stress mechanism of a cracked lining and reinforced layer is studied.The relationship between the performance parameters of the reinforced material and the mechanical characteristics of the structure is obtained.Thus,the requirements of reinforcement layer thickness and the mechanical properties of UHPC are obtained.On this basis,a calculation method for converting between the stress and internal force of solid elements is proposed,and the stress characteristics of the joint surface between the lining and reinforcing materials are analyzed using a finite difference numerical simulation method.Consequently,the requirement of bond strength between UHPC and ordinary concrete is obtained.The results indicate the following:(1)For linings with a bearing capacity loss of less than 40%,UHPC can be used for reinforcement.(2)For linings with no more than 15%bearing capacity losses,UHPC can reduce the thickness of the reinforced layer to about 10 cm.
作者
潘岳
贺雄飞
邹翀
杨朝帅
PAN Yue;HE Xiongfei;ZOU Chong;YANG Chaoshuai(Guangdong Provincial Key Laboratory of Intelligent Monitoring and Maintenance of Tunnel Structure,Guangzhou 511458,Guangdong,China;China Railway Tunnel Consultants Co.,Ltd.,Guangzhou 511458,Guangdong,China)
出处
《隧道建设(中英文)》
CSCD
北大核心
2022年第9期1647-1655,共9页
Tunnel Construction
关键词
UHPC
隧道二次衬砌
裂损整治
性能参数
ultra-high-performance concrete
tunnel secondary lining
crack treatment
performance parameter