期刊文献+

一种固液相变降膜式冷储能器的设计及其性能研究

Design and performance study of a solid-liquid phase change falling film cold energy storage device
下载PDF
导出
摘要 设计了一种新型的固液相变材料降膜式冷储能器,冷储能器由3组水平管柱组成,每组管柱由36根表面喷涂亲水涂层的铜管组成,采用癸酸、月桂酸和油酸混合物为相变材料,其相变温度为20℃左右。实验研究表明:该冷储能器具有良好的传热性能,泵功耗小;调整管束的列数或行数,可以简单地获得灵活的冷藏量;降低液膜雷诺数可以提高冷藏性能。 A new type of solid-liquid phase change material falling film cold energy storage device is designed.The cold energy storage device is composed of three groups of horizontal pipe strings,each group of pipe strings is equipped with 36 copper tubes with hydrophilic coating on the surface.A mixture of decanoic acid,lauric acid and oleic acid is adopted as the PCM whose phase change temperature is around 20℃.Experimental results show that this newly designed cold energy storage has good heat transfer performance and low pump power consumption.Flexible cold storage quantity can be simply obtained through adjusting the column or row number of the tube bundle.The lower film Reynolds number will strengthen the cold storage performance.
作者 肖红升 刘振华 Xiao Hongsheng;Liu Zhenhua(School of Mechanical Engineering,Nantong Vocational University,Jiangsu Nantong,226007,China;School of Mechanical and Power Engineering,Shanghai Jiaotong University,Shanghai,200240,China)
出处 《机械设计与制造工程》 2022年第9期110-114,共5页 Machine Design and Manufacturing Engineering
基金 江苏省自然科学基金面上项目(BK20191209) 南通市科技计划项目(JCZ21136)。
关键词 冷储能 相变材料 降膜 cold energy storage PCM falling film
  • 相关文献

参考文献1

二级参考文献13

  • 1徐征,刘筱屏,何海亮.温湿度独立控制空调系统节能性实例分析[J].暖通空调,2007,37(6):129-132. 被引量:24
  • 2Neksa P, Rekstad H, Zakeri G R, et al. CO2-heat pump water heater: characteristics, system design and experimental results[J]. International Journal of Refrigeration, 1998, 21(3): 172- 179.
  • 3Teng Y, Wang R Z, Wu J Y, Study of the funda- mentals of adsorption systems [J]. Applied Thermal Engineering, 1997, 17(4): 327-338.
  • 4Wang S G, Wang R Z, Li X R. Research and devel- opment of consolidated adsorbent for adsorption sys- tems[J]. Renewable Energy, 2005, 30: 1425-1441.
  • 5Darkwa J, Fraser S, Chow D H C. Theoretical and practical analysis of an integrated solar hot wate: powered absorption cooling system [J]. Energy, 2012, 39: 395-402.
  • 6Zhai X Q, Wang R Z. A review for absorbtion and adsorbtion solar cooling systems in China[J]. Renew- able and Sustainable Energy Reviews, 2009, 13: 1523 -1531.
  • 7Lu Y Z, Wang R Z, Zhang M, etal. Adsorption cold storage system with zeolite - water working pair used for locomotive air conditioning [J]. Energy Convers Manage, 2003, 44:1733- 1743.
  • 8Sharma A, Tyagi V V, Chen C R, et al. Review on thermal energy storage with phase change materials and applications [J]. Renewable Sustainable Energy Reviews, 2009, 13(2): 318 -345.
  • 9Roxas-Dimaano M N, Watanabe T. The capric and lauric acid mixture with chemical additives as latent heat storage materials for cooling application[J]. En- ergy, 2002, 27: 869-888.
  • 10Roxas-Dimaano M N, Watanabe T. The caprie-lauric acid and pentadecane combination as phase change material for cooling applications[J]. Applied Thermal Engineering, 2002, 22:365- 377.