摘要
针对风管送风式空调(热泵)机组室内机非出风口处外观面凝露现象,建立仿真模型并计算得到流场仿真云图,通过分析云图中气流通过低温源以及流经区域的流速,找到凝露区域,确定凝露传递路径,制定防凝露整改措施,将原凝露区域风速降至1 m/s以下,防凝露设计方案的可靠性得到提升。
Aiming at condensation phenomenon of appearance surface at non-outlet of indoor unit of ducted air-conditioning(heat pump)units,the simulation model is established and the simulation cloud chart of the flow field is calculated.By analyzing the velo-city of airflow through the low temperature source and through the region in the cloud chart,the condensation area is found,the condensation transmission path is determined;the anti-condensation rectification measures are made,and the flow rate in the condensation region is reduced below 1 m/s,which improves the reliability of the anti-condensation design.
作者
张荣海
颜鲁华
洪浩
Zhang Ronghai;Yan Luhua;Hong Hao(Qingdao Hisense Hitachi Air-conditioning Systems Co.,Ltd.)
出处
《制冷与空调》
2022年第9期17-20,共4页
Refrigeration and Air-Conditioning
关键词
风管送风式空调(热泵)机组
流场
风速
凝露
ducted air-conditioning(heat pump)unit
flow field
air velocity
condensation