某数据中心机房环境测试分析 被引量:2

Room Environment Test and Analysis of a Data Center
下载PDF
导出
摘要 本文以无锡创新园某数据机房为例,对机房内空气温湿度、洁净度进行测试分析,详细介绍了测试方法以及测试内容。并对测试数据结果与规范标准进行比对,发现检测中存在的问题,进一步提出改进措施和总结。为数据中心的建设,节能和合理运行提供参考。 Taking a data center of Wuxi Innovation Park as an example, this paper introduces the test method and test contents in detail to examine the actual temperature and humidity of the room. The results of the test data are compared with the standard, the problems in the test are analyzed, and the improvement measures and summary are put forwarded.It provides reference for the construction, energy saving and reasonable operation of data center.
作者 万鑫 周朝瑜 WAN Xin;ZHOU Chao-yu(College of Architecture and Environmental Engineering,Wuxi City College of Vocational;Wuxi Qingda Architectural Design Institute)
出处 《建筑热能通风空调》 2022年第9期63-65,共3页 Building Energy & Environment
基金 无锡市职业院校名师工作室资助项目(201812207)和校级科研专项(WXCY-2020-KY-16)
关键词 数据机房 环境测试 温湿度 洁净度 data center environment test temperature and humidity cleanliness
  • 相关文献

参考文献3

二级参考文献19

  • 1Malone C, Belady C. Metrics to characterize data center & IT equipment energy use[A] In: Proceedings of 2006 Digital PoWer Forum [C]. Richardson: TX, 2006.
  • 2电子信息系统机房设计规范(GB50174-2008)[S].北京:人民出版社,2008.
  • 3中国互联网信息中心.第37次中国互联网络发展状况统计报告[R/OL].(2016一01-22).http://www.chinaz, com/news/2016/0122/498650, shtml? uc_biz _str= S: custom I C. iflow_ncmt I K: true.
  • 4中国电子工程设计院,中国航空规划设计研究院.电子信息系统机房设计规范:GB50174-2008[S].北京:中国计划出版社,2009:2.
  • 5ISO. Information technology-data centres--key performance indicators: ISO/IEC 30134. 1 [S]. Switzerland. ISO/IEC, 2016 : 2.
  • 6BICSI. Data center design and implementation best practices: ANSI/BICSI 002 - 2014 [S]. Tampa.. BISCI, 2014.11.
  • 7TIA Technology & Standards Department. Telecommunications infrastructure standard for data centers.. TIA- 942 - A- 2014 [S]. Arlington: Elecommunications Industry Association Technology Standards Department, 2014 : 3.
  • 8ASHRAE. Design considerations for datacom equipment centers [ M ]. Atlanta: ASHRAE Inc, 2010:176.
  • 9U S Department of Commerce. Cloud computing synopsis and recommendations: NIST special publication 800 - 146 [R]. Gaithersburg.. Computer Security Division Information Technology Laboratory National Institute of Standards and Technology Gaithersburg, 2012 : 2-1.
  • 10工业和信息化部,发展改革委,国土资源部,等.关于数据中心建设布局的指导意见(工信部联通[2013]13号)[A/OL].(2013-01-11).http://www. miit gov. cn/n11293472/n11293832/ n12843926/n13917072/15121870, html.

共引文献37

同被引文献6

引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部