高校宿舍自然通风现状调查及不同测试方法分析 被引量:5

Investigation on the Current Situation of Natural Ventilation in College Dormitories and Analysis of Different Testing Methods
原文传递
导出
摘要 通风量是影响室内空气质量和建筑能耗最关键参数之一。为了确定宿舍在窗户开启和关闭等自然通风状态下的换气次数水平,同时分析目前最常用的2种换气次数测试方法(CO_(2)示踪气体衰减法、上升法)测试结果是否存在差别。本研究以人体产生的CO_(2)作为示踪气体,测试了38个学生宿舍样本在关窗和开窗条件下的通风情况,得到关窗换气次数介于0.18次/h和0.75次/h之间,平均为0.41次/h。开窗换气次数介于1.07次/h和8.21次/h之间,平均为3.74次/h。2种开关窗状态下的换气次数均服从对数正态分布。此外通过对比衰减法和上升法在关窗状态下的测试结果,发现两者存在显著差异,上升法测得的结果为衰减法的1.58倍,经过分析认为上升法的系统误差更大,其测试结果的可靠性低于衰减法。 Ventilation rate is one of the most critical parameters affecting indoor air quality and building energy consumption.In order to determine the air exchange rate in the dormitories and analyze the differences between the CO_(2) tracer gas decay method and build⁃up method,occupant⁃generated CO_(2) was used as a tracer gas,and the ventilation conditions of 38 student dormitory samples under window closed and open conditions were tested in this study.The air exchange rates under windows close condition varied between 0.18/h and 0.75/h,with an average value of 0.41/h.The air exchange rates when windows open varied between 1.07/h and 8.21/h,with an average of 3.74/h.The air exchange rates under these two different window opening behaviors were lognormal distributed.There were significant differences between the results of the decay method and the build⁃up method.The average infiltration rate by the build⁃up method was 1.58 times as the decay method.Analysis showed that the system error of the build⁃up method is larger,and therefore the reliability of this method is lower than the decay method.
作者 李民健 梁卫辉 LI Minjian;LIANG Weihui(Nanjing University,Nanjing 210093,China)
机构地区 南京大学
出处 《建筑科学》 CSCD 北大核心 2022年第10期216-221,共6页 Building Science
关键词 室内空气 自然通风 换气次数 衰减法 上升法 indoor air natural ventilation air exchange rate decay method build⁃up method
  • 相关文献

参考文献7

二级参考文献56

  • 1徐东群,尚兵,曹兆进.中国部分城市住宅室内空气中重要污染物的调查研究[J].卫生研究,2007,36(4):473-476. 被引量:70
  • 2国家统计局.中国统计年鉴2011[M].北京:中国统计出版社,2011.
  • 3朱奋飞,邵晓亮,李先庭.关于示踪气体法测量房间换气量的探讨[C]//全国暖通空调制冷2008年学术年会文集,2008.
  • 4Ing. Petra St'Ctvova. Experimental Evaluation of Ventilation in Dwellings by Tracer Gas CO2 [ D ]. Prague: Czech Technical University, 2011:24 - 32,70 - 82.
  • 5Stavova P, Melikov AK, Sundell J, et al. A new approach for ventilation measurement in homes based on CO2 produced by people--Laboratory study [ C ]//Proceedings of 17th Air- Conditioning and Ventilation Conference,Prague,2006.
  • 6Yoshino H. Experimental study of the multi-zonal airflow measurement method using human expiration [ J ]. Journal of Environmental Engineering ( Transaction of AIJ ), 2010, 75 (652) :499 - 508.
  • 7Laussmann D, Helm D. Air change measurements using tracer gases [ J ] [ EB/OL ]. http://edoc, rki. de/oa/articles/ revSFJQq98 Qgc/PDF/27 OA2TGPWvvO. pdf.
  • 8ASHRAE. 2009 ASHRAE Handbook--Fundamentals [ M ]. Atlanta: American Society of Heating, Refrigerating and Air- Conditioning Engineers ,2009.
  • 9Dimitroulopoulou C. Ventilation in Europeandwellings : a review[J]. Building and Environment,2012,47(1): 109-125.
  • 10Seppanen O A, Fisk W J, Mendell M J. Associationof ventilation rates and CO2 concentrations withhealth and other responses in commercial andinstitutional buildings[J]. Indoor Air, 1999,9(4):226-252.

共引文献97

同被引文献35

引证文献5

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部