摘要
针对一起110 kV油浸式电流互感器爆炸事故,通过对事故电流互感器进行解体检查、分析保护装置的动作情况,明确了故障原因是电流互感器末屏接地断开,并提出开展油浸式电流互感器在线监测等防范措施,以防止油浸式电流互感器发生同类缺陷。
In allusion to an explosion accident of a 110 kV oil-immersed current transformer,it is determined that the fault cause is grounding disconnection of the current transformer end screen through the disassembly inspection of the faulty current transformer and the analysis of the operation of relay protection device.The preventive measures such as carrying out online monitoring of the oil-immersed current transformer are put forward to prevent the similar defect of the oil-immersed current transformer.
作者
李培
王理强
郭祥雄
李宏博
郭良峰
LI Pei;WANG Liqiang;GUO Xiangxiong;LI Hongbo;GUO Liangfeng(State Grid of China Technology College,Jinan 250002,China;State Grid Wuhan Electric Power Supply Company,Wuhan430056,China)
出处
《山东电力高等专科学校学报》
2022年第5期32-35,共4页
Journal of Shandong Electric Power College
关键词
油浸式电流互感器
一次绕组
故障分析
oil-immersed current transformer
primary winding
fault analysis