期刊文献+

钢管混凝土K形节点应力集中系数计算方法 被引量:1

Calculation method of stress concentration factor for CFST K-joint
下载PDF
导出
摘要 以钢管混凝土K形(CFST-K)节点为研究对象,进行了7个CFST-K形节点和1个钢管K形(ST-K)节点足尺模型试验和实体有限元分析;分析了现有CFST-K形节点应力集中系数的适用性;基于管内混凝土约束作用对CFST-K形节点变形形态的影响,提出了CFST-K形节点应力集中系数的缓解系数,并采用理论分析方法推导得到考虑管内混凝土约束作用的CFST-K形节点应力集中系数计算方法。结果表明:CFST-K形节点的最大应力集中系数均出现在受拉支管与主管相贯焊缝靠近主管侧冠点位置;CFST-K形节点应力集中系数与壁厚比呈正相关关系,而径厚比与管径比对CFST-K形节点应力集中系数影响较小;CFST-K形和ST-K形节点最大应力集中系数分别为3.98和6.08,管内混凝土能使CFST-K形节点应力集中系数下降约34.5%。现有CFST-K形和ST-K形节点应力集中系数计算方法未能充分考虑管内混凝土约束作用对CFST-K形节点应力集中系数的影响,且未考虑几何参数之间的耦合关系,采用其进行CFST-K形节点应力集中系数计算时精度较低;所提出的考虑管内混凝土约束作用的CFST-K形节点应力集中系数计算方法可将计算误差由现有计算方法的58.0%降低至19.6%。 With the concrete filled steel tube K-shaped(CFST-K) joint taken as the research object, full-scale model tests and solid finite element analysis on seven CFST-K joints and one steel tube K-shaped(ST-K) joint were carried out. The applicability of existing stress concentration factors(SCF) of CFST-K joints was analyzed. Based on the effect of concrete constraint in tube on the deformation morphology of CFST-K joints, the relief coefficient of SCF for CFST-K joint was proposed, and the calculation method of SCF of CFST-K joints considering concrete constraint in tube was derived by theoretical analysis. The results show that the maximum SCFs of CFST-K joints all appear in the position of the intersecting weld between branch tube in tension and main tube near the crown point of main tube. The SCF of CFST-K joints is positively correlated with the wall thickness ratio, while the diameter-thickness ratio and tube diameter ratio have little influence on the SCF of CFST-K joints. The maximum SCFs of CFST-K and ST-K joints are 3.98 and 6.08, respectively, and the concrete in tube can reduce the SCF of CFST-K joints by about 34.5%. The existing calculation methods for the SCF of CFST-K and ST-K joints fail to fully consider the influence of concrete constraint in tube on the SCF of CFST-K joints, and fail to consider the coupling relationship between geometric parameters, so the accuracies of the SCF of CFST-K joints calculated by these methods are generally low. With the proposed method, the calculation error of the SCF of CFST-K joint can be reduced from 58.0% to 19.6%.
作者 陈康明 黄汉辉 吴庆雄 郑樵风 Chen Kangming;Huang Hanhui;Wu Qingxiong;Zheng Qiaofeng(College of Civil Engineering,Fuzhou University,Fuzhou 350116,China;Fujian Provincial Key Laboratory on Multi-Disasters Prevention and Mitigation in Civil Engineering,Fuzhou University,Fuzhou 350116,China;Fujian Key Laboratory of Engineering Structures,Fuzhou University,Fuzhou 350116,China)
出处 《土木工程学报》 EI CSCD 北大核心 2022年第12期94-104,共11页 China Civil Engineering Journal
基金 国家重点研发计划(2017YFE0130300) 国家自然科学基金(52078137) 福建省自然科学基金杰青项目(2019J06009) 福州市科技局产学研项目(2020-GX-27)。
关键词 钢管混凝土K形节点 应力集中系数 缓解系数 理论推导 计算方法 concrete filled steel tubular K-joint stress concentration factor relief coefficient theoretical derivation calculation method
  • 相关文献

参考文献8

二级参考文献61

共引文献118

同被引文献16

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部