期刊文献+

空调器用翅片管式换热器排水性能试验研究 被引量:2

Drainage performance test of finned-tube heat exchanger of air conditioner
下载PDF
导出
摘要 采用动态浸渍法对Ф7 mm翅片管式换热器的排水性能进行试验研究,并分析存水量对换热器性能的影响。结果表明,换热器安装倾斜角为45°~60°时的排水性能较好;翅片片型和翅片宽度是提升换热器排水性能的关键;对2种排水特性的换热器性能进行试验对比,发现排水性能好的换热器在湿工况下的性能更好。 The drainage performance of Ф7 mm finned-tube heat exchanger is studied by dynamic impregnation method, and the effect of water retention on the performance of heat exchangers is analyzed. The results show that the drainage performance of the heat exchangers is better when the installation inclination angle is 45°-60°. The shape and width of fin are key factors to improve the drainage performance of heat exchangers. The performances of two heat exchangers with different drainage characteristics are compared and it is found that the heat exchangers with better drainage performance also have better performance under wet conditions.
作者 刘晓蕾 孟建军 蔡良烽 赵东方 李晓宇 Liu Xiaolei;Meng Jianjun;Cai Liangfeng;Zhao Dongfang;Li Xiaoyu(Qingdao Hisense Hitachi Air-conditioning Systems Co,Ltd.)
出处 《制冷与空调》 2022年第12期55-59,共5页 Refrigeration and Air-Conditioning
关键词 空调器 换热器 排水性能 安装角度 翅片 air conditioner heat exchanger drainage performance installation angle fin
  • 相关文献

参考文献4

二级参考文献23

  • 1慎利峰,闵敬春,高屹峰,郑永新.铜翅片蒸发器的亲水处理及制冷性能评价[J].工程热物理学报,2007,28(z2):105-108. 被引量:3
  • 2王伟,路伟鹏,董兴国,冯颖超.不同表面特性下翅片管换热器排水性能的实验研究[J].建筑科学,2012,28(S2):109-112. 被引量:3
  • 3杨强,戴立生.蒸发器亲水性对空调性能影响的试验研究[J].制冷学报,2007,28(3):6-10. 被引量:9
  • 4WU X M, WEBB R L. Investigation of the Possibility of Frost Release from a Cold Surface[J]. Experimental Thermal and Fluid Science, 2001, 24(3-4): 151-156.
  • 5MIN J, WEBB R L. Condensate formation and drainage on typical fin materials[J]. Experimental Thermal and Fluid Science, 2001.25(3-4): 101-111.
  • 6WU X M, WEBB R L. Investigation of possible frost release from a cold surface[J]. Experimental Thermal and Fluid Science, 2001, 24(3): 156-161.
  • 7LIU L, JACOBI A M. Air-side surface wettability effects on the performance of slit-fin-and-tube heat exchangers operating under wet-surface conditions[J]. Journal of Heat Transfer, 2009, 131 (5): 051802.
  • 8LIU L, JACOBI A M. Issues affecting the reliability of dynamic dip testing as a method to assess the condensate drainage behavior from the air-side surface of dehumidifying heat exchangers[J]. Experimental Thermal and Fluid Science, 2008, 32(8): 1512-1522.
  • 9MCLAUGHLIN W J. The Effect of Condensate on the Air Side Performance of Louver Fin AutomotiveEvaporators[D]. Pennsylvania State University, 1999.
  • 10LIU L, JACOBI A M. The effects of hydrophilicity on water drainage and condensate retention on air-conditioning evaporators[C]. The l lth International Refrigeration and Air Conditioning Conference at Purdue West Lafayette, July 17-20, 2006.