期刊文献+

影响冷却器换热效果的原因分析及应用

Cause Analysis and Application on Influence of Heat Exchange Efficiency of Cooler
下载PDF
导出
摘要 针对空分空压机油冷却器、电机冷却器换热效果差,导致油温、电机进风温度偏高等问题,对影响冷却器换热效果的原因进行了分析,找到的关键原因是循环水系统结垢、腐蚀铁锈和黏泥填料碎片等杂质造成了换热设备细管子堵塞,通过物理清洗、化学清洗并将循环冷却水调整为pH 5~5.5,很好地解决了冷却器换热效果差的问题,换热工况良好。 The heat exchange efficiency of oil cooler, motor cooler of air separation compressor in one enterprise is poor, it caused high oil temperature and high inlet air temperature of motor and the other problems, so we analyzed the reasons of the influence factors for heat exchange efficiency of coolers, the critical reasons were scaling of circulating water system, corrosive rust, slime filler fragments and the other impurities blocking of the thin tubes of heat exchange devices, the physical cleaning and chemical cleaning were adopted and the p H value of circulating cooling water were adjusted to 5 ~5.5, the problem that poor heat exchange efficiency was well resolved, the heat exchange working conditions were good.
作者 王利荣 WANG Li-rong(Southwest Copper Branch,Yunnan Copper(Group)Co.,Ltd.,Kunming,Yunnan 650102,China)
出处 《云南冶金》 2022年第6期195-198,共4页 Yunnan Metallurgy
关键词 冷却器 换热效果 结垢 物理清洗 化学清洗 cooler heat exchange efficiency scaling physical cleaning chemical cleaning
  • 相关文献

参考文献1

二级参考文献12

  • 1傅磊,陈与德.精确计算多组分体系配合物稳定常数的程序[J].铀矿冶,1989,8(2):29-34. 被引量:9
  • 2MM Rreedy, G H Nacollas. [J].Desalination, 1973,12:61-73.
  • 3汪祖模.水质稳定剂[M].上海:华东华工出版社,1996..
  • 4G H Nacollas, MM Rreedy. [J].J Colloid Interface Sci. 37(1971)824-830.
  • 5G H Nacollas.[J].Adv. Colloid Interface Sci.1979,10:215-52.
  • 6C D Gabrielli, et aL. [J].J. CrystalGrowth. 1999,200:236-250.
  • 7Motekaitis R J, Martell A E. [J].Can J. Chem.1982,60:2403.
  • 8AEMartell and R J Motekaitis. [C].2nd Ed. VCH.New-York. 1992.
  • 9Stella Lacour, et al. [J].Talanta 46(1998)999-1009.
  • 10HMIrving,MGMiles, LDPettit. [J].Analy. Chimi.Acta, 38(1967)475-488.