期刊文献+

单元式直接蒸发冷却空调机组应用实测及分析 被引量:1

Test and analysis on unit direct evaporative cooling air-conditioning unit
下载PDF
导出
摘要 对应用于西安某地铁高架站台的单元式直接蒸发冷却空调机组进行实际测试,结果表明,该机组的直接蒸发冷却效率可达86.5%,峰值制冷量为21.54 kW,最佳能效比可达到12.73,其送风口最高风速可达10.6 m/s,送风范围可达9.7 m,进出风口的PM10和PM2.5均可达到GB 3095—2012《环境空气质量标准》中的一级浓度标准。 The actual test on the unit direct evaporative cooling air-conditioning unit in a subway elevated platform in Xi’an is conducted. The result shows that the direct evaporative cooling efficiency of the unit can reach 86.5%, the peak cooling capacity is 21.54 kW, and the best energy efficiency ratio can reach 12.73. The maximum wind speed of the air supply outlet can reach 10.6 m/s, and the air supply range can reach 9.7 m. The PM10and PM2.5of the air inlet/outlet can reach the level 1 concentration standard in the GB 3095-2012 Ambient air quality standard.
作者 史东旭 黄翔 王红利 武茁苗 张文锦 Shi Dongxu;Huang Xiang;Wang Hongli;Wu Zhuomiao;Zhang Wenjin(Xi'an Polytechnie University;Aolan(Fujian)Industry Co.,Ltd.)
出处 《制冷与空调》 2023年第1期46-49,共4页 Refrigeration and Air-Conditioning
关键词 地铁站 蒸发冷却 空气温湿度 送风范围 空气品质 subway station evaporative cooling air temperature and humidity air supply range air quality
  • 相关文献

参考文献8

二级参考文献65

共引文献42

同被引文献6

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部