一起3/2接线方式敞开式隔离开关发热故障分析 被引量:1

Heating Fault Analysis of Open-type Isolation Switch under 3/2 Connection Mode
下载PDF
导出
摘要 文中主要针对一起3/2接线方式隔离开关接触不良引起保护装置异常事件,从3/2接线方式等值电路、电流分配、接触电阻增大和线路负载变化所引起接触点温升特性等方面进行分析,并与双母线接线方式中隔离开关接触不良引起温升特性进行对比,得出3/2接线方式中隔离开关接触不良所引起接触点温升特性与负荷变化、标准回路电阻变化的对应关系和差异。 Aiming at an abnormal event of protection device caused by poor contact of isolation switch under 3/2 connection mode, the characteristics of contact temperature rise caused by the equal circuit under 3/2 connection mode, current distribution, the increase of contact resistance and line load are analyzed. The characteristics are compared with that of temperature rise caused by poor contact of isolation switch under double bus connection mode. The relationship and differences between contact temperature rise caused by poor contact of isolation switch and the change of load and preferred circuit resistance under 3/2 connection mode are obtained.
作者 王来源 雷昌成 WANG Laiyuan;LEI Changcheng(Ultra-high Voltage Company of State Grid Ningxia Electric Power Co.,Ltd.,Yichuan 750011,Ningxia,China)
出处 《四川电力技术》 2023年第1期90-94,共5页 Sichuan Electric Power Technology
关键词 隔离开关 3/2接线 接触电阻 温升极限 isolation switch 3/2 connection contact resistance temperature rise limit