摘要 针对国网吉林供电公司66 kV新城变电站10 kV电压互感器高压侧熔丝短期内频繁熔断的现象,分析了配电系统中电磁式电压互感器铁磁谐振过电压的产生机理,提出3种抑制铁磁谐振的方法并进行了比较,为今后的系统升级改造提供参考。 In view of the frequent fusing of the high-voltage side fuse of the 10 kV voltage transformer in the 66 kV Xincheng substation of State Grid Jilin power supply company in a short period of time,this paper analyzes on the generation mechanism of the ferromagnetic resonance overvoltage of the electromagnetic voltage transformer in the distribution system,puts forward and compares three methods for restraining the ferromagnetic resonance,with a view to providing reference for the system upgrading and reconstruction in the future.
作者 刘宏伟 张航 LIU Hongwei;ZHANG Hang(State Grid Jilin Electric Power Co.,Ltd.Jilin Power Supply Company,Jilin 132012,China)
出处 《黑龙江电力》 CAS 2023年第1期64-66,共3页 Heilongjiang Electric Power
关键词 电磁式电压互感器 铁磁谐振 消谐装置 electromagnetic voltage transformer ferromagnetic resonance resonance elimination device