摘要
在新能源场站配置同步调相机是提升新能源送出能力的有效措施,但也给系统带来了暂态功角失稳的风险。首先,通过网络化简,建立新能源场站同步调相机暂态分析数学模型。然后,分析新能源动态影响下同步调相机的暂态功角失稳形态,基于等面积定则解释其失稳机理并提出暂态失稳判据。最后,通过实际新能源送出系统的简化模型和IEEE 39节点改进系统仿真验证了理论分析的有效性。结果表明,无论新能源低电压穿越控制深度高低,新能源场站附近部署的同步调相机均有暂态功角加速失稳的风险,需要在新能源送出系统的配置规划及运行控制中予以考虑。
The configuration of the synchronous condenser(SC) in the renewable energy station is an effective measure to improve the transmission capacity of renewable energy, but it also brings the risk of transient angle instability to the system. First, through the network simplification, the transient analysis mathematical model of SCs in the renewable energy station is established. Then,the transient power angle instability mode of SC is analyzed under the dynamic influence of renewable energy. The instability mechanism is explained and the criterion of transient instability is proposed based on the equal area criterion. Finally, the effectiveness of the theoretical analysis is verified through the simplified model of the actual renewable energy sending system and the improved IEEE 39-bus system simulation. Results show that the SC deployed near a renewable energy station has the risk of transient power angle accelerating instability,no matter the control depth of renewable energy low voltage ride-through is low or high, which needs to be considered in the configuration planning and operation control of renewable energy sending system.
作者
杨松浩
李秉芳
赵天骐
赵伟
徐鹏
谢欢
YANG Songhao;LI Bingfang;ZHAO Tianqi;ZHAO Wei;XU Peng;XIE Huan(School of Electrical Engineering,Xi'an Jiaotong University,Xi'an 710049,China;North China Electric Power Research Institute Co.,Ltd.,Beijing 100045,China;North China Branch of State Grid Corporation of China,Beijing 100053,China)
出处
《电力系统自动化》
EI
CSCD
北大核心
2023年第3期12-18,共7页
Automation of Electric Power Systems
基金
国家自然科学基金资助项目(52007143)
中国博士后科学基金资助项目(2021M692526)。
关键词
同步调相机
新能源场站
暂态稳定性
等面积定则
暂态失稳机理
synchronous condenser
renewable energy station
transient stability
equal area criterion
transient instability mechanism