摘要
针对500 kV长寿变电站主变抗短路电流能力不足的问题,分析主变抗短路电流能力提升的不同方法。分析限流电抗器阻抗值确定的原则,结合站内电气布置,采用在主变低压侧汇流前加装干式限流电抗器,结合低压侧连接导体绝缘化的处理方案。仿真计算表明加装限流电抗器后,低压侧电压波动不影响站内设备运行,无功补偿容量小幅偏差的影响可控。结果表明:该方案为一种经济而可靠的主变抗短路能力不足治理方案。
Aimed at the problem of the transformer in 500 kV Changshou substation,different methods of improving anti-short circuit ability is analyzed.The principle of determining the impedance of the current-limiting reactor is analyzed.According to the layout of the substation,installation of dry current-limiting reactor before confluence on the low-voltage side of the transformer,combined with insulation of the connecting conductor is adopted.The simulation calculation shows after installation the current-limiting reactor,voltage fluctuation on the low-voltage side do not affect the equipment operation;the influence of slight deviation of the reactive power compensation is controllable.The results show it is an economical and reliable solution for insufficient anti-short circuit ability of the main transformer.
作者
邢毅
骆玲
张朝煜
张文韬
XING Yi;LUO Ling;ZHANG Chaoyu;ZHANG Wentao(Southwest Electric Power Design Institute Co.,Ltd.of China Power Engineering Consulting Group,Chengdu 610021,China)
出处
《电力勘测设计》
2023年第3期27-31,共5页
Electric Power Survey & Design
关键词
在运主变压器
抗短路能力
限流电抗器
电压波动
无功补偿
main transformer in operation
anti-short circuit ability
current-limiting reactor
voltage fluctuation
reactive compensation