期刊文献+

闭式循环冷却水系统总铁超标原因分析及解决对策

Cause Analysis and Solutions of Excess Iron in Closed Circulation Cooling Water System
下载PDF
导出
摘要 西北地区某煤化工企业应用了闭式循环冷却水系统,并采用除盐水作为补充水,系统运行过程中循环水总铁始终偏高,长期超过国标《工业循环冷却水处理设计规范》(GB50050—2017)规定≤2 mg·L^(-1)的要求,存在比较严重的腐蚀问题。针对该煤化工企业闭式循环冷却水总铁超标问题,分析了循环水总铁浓度超标原因,并从优化水处理药剂配方、调节循环水pH、改变加药方式、加强微生物控制4个方面提出有效解决措施,为同行企业提供参考借鉴。 A coal chemical enterprise in northwest China adopts a closed circulation cooling device,and the closed circulating water uses desalted water as supplementary water.During the operation of the system,the total iron in circulating water was always on the high side,which exceeded the requirement of≤2 mg·L^(-1)stipulated in Design Code for the Treatment of Industrial circulating Cooling Water(GB50050—2017)for a long time,and there were serious corrosion problems.In this paper,in view of the problem of the total iron in the closed circulating cooling water exceeding the standard in the process of the coal chemical enterprise,the causes of the total iron mass concentration in the circulating water exceeding the standard were analyzed.And effective solutions were proposed from four aspects:optimizing the formulation of water treatment agents,adjusting the pH of the circulating water,changing the dosing method and strengthening the microbial control,so as to provide reference for the peer enterprises.
作者 武斌斌 王雪清 甄毅 WU Bin-bin;WANG Xue-qing;ZHEN Yi(Zhongtian Synergetic Energy Co.,Ltd.,Ordos Inner Mongolia 017399,China;Sinopec Dalian Research Institute of Petroleum and Petrochemicals Co.,Ltd.,Dalian Liaoning 116045,China)
出处 《当代化工》 CAS 2023年第2期386-389,共4页 Contemporary Chemical Industry
关键词 闭式循环冷却水 总铁 腐蚀 Closed circulating cooling water Total iron Corrosion
  • 相关文献

参考文献11

二级参考文献38

共引文献48

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部