期刊文献+

基于多电容接地方式的低压直流微电网故障定位 被引量:3

Fault Location for Low-voltage DC Microgrid Based on Multi-capacitor Grounding Scheme
下载PDF
导出
摘要 为提高低压直流微电网故障定位的准确性,提高电力系统运行的可靠性,提出一种基于多电容接地方式的低压直流微电网故障定位方法。首先,运用从馈线端子和接地电容器获得瞬时电流和电压,推导了直流微电网一般故障馈线的数学模型。其次,利用基于非线性优化方法的故障测距算法对故障及相关故障电阻进行了精确定位,并通过评估接地电容器在故障期间的响应,计算故障的准确距离。最后,通过搭建直流微电网实验室模型对所提方法的可靠性及有效性进行验证,实验结果表明所提方法具有较高的故障定位准确性。 To improve the fault location accuracy of low-voltage DC microgrid and the operation reliability of power sys⁃tem,a fault location method for low-voltage DC microgrid based on a multi-capacitor grounding scheme is proposed.First,a mathematical model of general fault feeder in DC microgrid is derived according to the instantaneous current and voltage obtained from feeder terminals and grounding capacitors.Second,the fault location algorithm based on the nonlinear optimization method is used to accurately locate the fault and the related fault resistance,and the accurate fault distance is calculated by evaluating the response of the grounding capacitor under the fault.Finally,the reliability and effectiveness of the proposed method are verified by building a DC microgrid laboratory model,and experimental re⁃sults show that this method has a high fault location accuracy.
作者 李英超 LI Yingchao(State Grid Heze Power Supply Company,Heze 274000,China)
出处 《电力系统及其自动化学报》 CSCD 北大核心 2023年第4期59-67,共9页 Proceedings of the CSU-EPSA
基金 国家电网基金资助项目(SGHEHS00FCJS1900440)。
关键词 电容接地 低压直流微电网 故障定位 故障暂态 非线性优化 capacitor grounding low-voltage DC microgrid fault location fault transient nonlinear optimization
  • 相关文献

参考文献13

二级参考文献211

共引文献328

同被引文献66

引证文献3

二级引证文献3

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部