数据中心气流组织特性及节能改造方案研究 被引量:2

Research on air distribution characteristics and energy saving reform schemes of data center
下载PDF
导出
摘要 针对数据中心机房由于机架上架率不同、气流组织分布不均匀等原因导致局部热点现象严重、末端空调设备长时间高负荷运行造成大量能耗浪费的问题,以夏热冬暖地区某数据中心机房为研究对象,利用CFD模拟软件,分析数据中心机房热环境温度场分布特征,利用机架冷却指数(RCI)、回风温度指数(RTI)、供热指数(SHI)及掺混指数(IOM)4种不同性能指标,评价3种不同节能改造方案的优劣。在此基础上,通过调节风柜频率,探讨不同供风量对机房热环境的影响。结果表明,提出的第三种方案能够有效改善机房热环境,减少供风能耗。 Taking a data center computer room in a hot summer and warm winter area as the research object,CFD simulation software was used to analyze its distribution characteristics of the thermal environment temperature field,and four different performance indicators were chosen to evaluate the advantages and disadvantages of three different energy-saving transformation schemes:frame cooling index(RCI),return air temperature index(RTI),heating index(SHI)and mixing index(IOM).On this basis,the influence of different air supply volume on the thermal environment of the machine room was discussed by adjusting the frequency of the air cabinet.The results show that the third scheme can effectively improve the thermal environment uniformity and reduce the energy consumption of air supply.
作者 闫军威 陈汉忠 周璇 徐志立 吴一心 Yan Junwei;Chen Hanzhong;Zhou Xuan;Xu Zhili;Wu Yixin(School of Mechanical&Automotive Engineering,South China University of Technology,Guangzhou 510641,China)
出处 《低温工程》 CAS CSCD 北大核心 2023年第2期61-69,共9页 Cryogenics
基金 广东省自然科学基金资助项目(2022A1515011128、2019A1515011518)。
关键词 数据中心 计算流体力学 上架率 气流组织 供风量 data center computational fluid dynamics(CFD) loading rate air distribution optimization air supply volume
  • 相关文献

参考文献7

二级参考文献86

共引文献178

同被引文献9

引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部