期刊文献+

寒冷地区土壤源热泵系统冬季运行特性分析

Analysis of winter operation characteristics of ground source heat pump system in cold regions
下载PDF
导出
摘要 以石家庄市某土壤源热泵项目为研究对象,通过对冬季运行工况的实时监测,分析了土壤源热泵系统在石家庄市的运行性能和该项目的运行效果。结果表明:负荷侧和地源侧供回水温度的变化均会受到室外气温的影响,且负荷侧回水温度和地源测供水温度受到的影响更大;冬季工况下,机组平均COP为4.2,系统平均COP为2.9;当环境温度低于4℃时,机组COP变化幅度较大,为45%左右。土壤源热泵系统在用能效益、经济效益以及环境效益方面均有良好表现:制热工况下节能率为31.62%;静态投资回收年限为8.54年;全年每平方米可减少二氧化碳排放21 kg,减少二氧化硫排放0.17 kg,减少粉尘排放0.09 kg。 Taking a ground-source heat pump project in Shijiazhuang as the research object,through real-time monitoring of winter operating conditions,the operation performance of the groundsource heat pump system in Shijiazhuang and the operation effect of the project are analyzed.The results show that the change of water supply and return temperature at the load side and the ground source side would be affected by the outdoor air temperature,and the return water temperature at the load side and the water supply temperature measured by the ground source would be affected more significantly;Under winter conditions,the average COP of the unit is 4.2,and the average COP of the system is 2.9;When the ambient temperature is lower than 4 C,the COP of the unit changes greatly,about 45%.The ground-source heat pump system has good performance in terms of energy efficiency,economic efficiency and environmental efficiency:the energy saving rate under heating conditions is 31.62%;The static investment payback period is 8.54 years;The annual emission per square meter can reduce 21kg of carbon dioxide,0.17 kg of sulfur dioxide and 0.09 kg of dust.
作者 陈俊亦 CHEN Junyi(Karamay Thermal Power Co.,Ltd.,Karamay 834000,China)
出处 《区域供热》 2023年第2期59-62,63,78,共6页 District Heating
关键词 土壤源热泵 运行特性 制热工况 室外温度 ground source heat pump operating characteristics heating condition outdoor temperature
  • 相关文献

参考文献7

二级参考文献68

共引文献21

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部