期刊文献+

110kV断路器防跳回路异常分析及优化改进 被引量:1

Abnormal Analysis and Optimization Improvement of Anti-Trip Circuit for 110 kV Circuit Breaker
下载PDF
导出
摘要 盘县电厂原110kV土焦I回线107间隔使用的LW29-126/T3150-40G型断路器,配备PSL-621型保护装置。该型号断路器无本体防跳回路,采用的是操作箱防跳回路,而该回路断路器远方/就地按钮打在就地及断路器机构存在故障时,存在断路器跳跃风险,同时此开关本体存在隐患,因此将原110 kV断路器升级换型为具有断路器本体防跳功能的3PA1-FG型断路器。但更换断路器后,按照原有接线方式会出现操作箱防跳回路与断路器本体防跳回路同时运行,产生寄生回路,为电力系统的安全稳定运行埋下事故隐患。针对上述问题,对断路器防跳回路进行了优化改进。 LW29-126/T3150-40G circuit breaker used at 107 intervals of the original 110 kV Tujiao I loop in Panxian Power Plant,equipped with PSL-621 protection device.This type of circuit breaker has no body anti-trip circuit,it uses operation box anti-trip circuit.The risk of circuit breaker tripping occurs when the remote/in-place buttons of the circuit breaker are hit in-place and the breaker mechanism fails.At the same time,there is a hidden danger in the switch body.Therefore,the original 110 kV circuit breaker was upgraded to a 3PA1-FG type circuit breaker with anti-trip function of the circuit breaker body.However,after replacing the circuit breaker,according to the original wiring method,the anti-trip circuit of the operation box and the anti-trip circuit of the circuit breaker body will operate at the same time,resulting in parasitic circuits,burying hidden dangers for the safe and stable operation of the power system.In view of the above problems,the anti-trip circuit of the circuit breaker is optimized and improved.
作者 晏和赓 YAN Hegeng(Guizhou Panjiang Power Investment Engineering Co.,Ltd.,Qianxinan 562400,China)
出处 《电工技术》 2023年第9期98-100,共3页 Electric Engineering
关键词 断路器 防跳回路 操作机构箱 优化改进 circuit breaker anti-trip circuit operation box optimization and improvement
  • 相关文献

参考文献9

二级参考文献26

共引文献47

同被引文献10

引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部