摘要
本文介绍了复合绝缘子发热背景与影响红外测温结果的主要原因,通过应用多种红外测温设备对粤东某的500 kV输电线路进行大量红外测温并记录分析结果。大量数据表明,测温距离是影响红外测温结果准确与否的重要影响因素,无人机测温较以往的手持测温设备测温更准确,6 m的测温距离是无人机红外测温的最佳测绝缘子温度距离。
This paper examines the heating background of composite insulators and the factors that influence infrared temperature measurements.The study utilizes various infrared temperature measurement equipment to conduct extensive measurements on a 500 kV transmission line in eastern Guangdong and record the resultant analysis.The data indicates that the temperature measurement distance significantly impacts the accuracy of the infrared temperature measurement results.Additionally,using a UAV for temperature measurement yields more precise results than using previous handheld temperature measurement equipment.Ultimately,the optimal insulator temperature measurement distance for UAV infrared measurements is found to be 6 m.
作者
关健
杨赞伟
杨思元
林来鑫
GUAN Jian;YANG Zanwei;YANG Siyuan;LIN Laixin(Shantou Power Supply Bureau of Guangdong Power Grid Co.,Ltd.,Shantou,Guangdong 515000,China)
出处
《自动化应用》
2023年第9期188-190,共3页
Automation Application
基金
广东电网有限责任公司汕头供电局(030819KK63371522)。
关键词
复合绝缘子
红外测温
距离
输电线路
composite insulator
infrared temperature measurement
distance