期刊文献+

RF-based location of partial discharge sources using received signal features

原文传递
导出
摘要 Partial discharges(PDs)are symptomatic of some localised defects in the insulation system of electrical equipment.PD activity emits electrical pulses in the form of radio frequency(RF)signals which can be captured using appropriate sensors.The analysis of the measured RF signals facilitates localisation of PD.This study investigates the plausibility of using purely RF received signal features of PD pulses to locate PD at low cost.A localisation approach based on the analysis of these features has been developed,with the assumption that PDs generate unique RF spatial patterns due to the complexities and nonlinearities of RF propagation.In this approach,two distinct frequency bands which hold different PD information are exploited.PD location features are extracted from the main PD signal and the two sub-band signals.Correlation-based feature selection(CFS)is employed for feature selection and dimensionality reduction.Experimental results show that PD location can be inferred from the features of the PD pulses.The application of CFS to PD data reduces the memory/computational demand and improves localisation accuracy.
出处 《High Voltage》 SCIE EI 2019年第1期28-32,共5页 高电压(英文)
  • 相关文献

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部