摘要 In this study,a simulation model of surface charge accumulation has been established.The model considers three accumulation ways,i.e.electrical conduction within the gas,through insulator volume and along the insulator surface.The generation,diffusion,drift and recombination of charge carriers are also taken into account.Based on it,the influence of polarity reversal,reversal time on surface charge and electric field distribution on a basin-type insulator are studied.The polarity of the surface charges and the direction of the electric field change after the voltage polarity reversal.When the preload voltage is equal to reversal voltage,the surface charge and the electric field distributions at steady state before and after voltage polarity reversal are all the same with opposite sign,and not affected by the reversal time.However,the time to reach the steady state varies with different reversal time.The steady-state surface charge and electric field increased with the rise of reversal voltage.The transient normal and tangential electric field would not exceed the value of the steady state,which means voltage polarity reversal has no additional influence on insulation performance.This research can provide guidance to the design and manufacture of DC GIS/GIL.
出处 《High Voltage》 SCIE EI 2020年第2期151-159,共9页 高电压(英文)
基金 the financial support from the National Natural Science Foundation of China(51877156) the Young Elite Scientists Sponsorship Program by CSEE(2018025).
  • 相关文献

同被引文献30

引证文献3

二级引证文献2

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部