期刊文献+

Prediction of radio interference from HVDC transmission lines based on corona discharge characteristics

原文传递
导出
摘要 Many research works have proved that it is viable to predict the radio interference (RI) of high-voltage alternating current transmission lines by corona cage test. However, it is uncertain whether the same method can be adopted for RI prediction of high-voltage direct current (HVDC) transmission lines, since the corona performance of HVDC lines is obviously affected by the widely distributed space charge. In this study, the detailed corona current characteristics, such as the current pulse amplitude, rise time, half-wave time, and repetition frequency are systematically studied by the reduced-scale experiment and the relationship between the average corona current and the RI excitation current is confirmed. Furthermore, based on the experimental study, a method for predicting the RI level of HVDC transmission lines by the corona cage test is proposed. The RI level of a ±800 kV bipolar HVDC transmission line is predicted and compared with the measured result, which verifies the validity of the proposed method.
出处 《High Voltage》 SCIE EI 2020年第6期679-687,共9页 高电压(英文)
基金 the Open Fund of State Key Laboratory of Power Grid Environmental Protection(No.GYW51201801176).