新型126kV SF_(6)/N_(2) GIS研制

Development of New Type 126kV SF_(6)/N_(2) GIS
下载PDF
导出
摘要 SF_(6)/N_(2)混合气体和纯SF_(6)相比,具有绿色环保、液化温度低、绝缘性能好及经济等优点。对SF_(6)/N_(2)混合气体绝缘性能的研究表明:SF_(6)体积占比为30%时的SF_(6)/N_(2)混合气体击穿强度要达到纯SF_(6)气体的击穿强度,压力应为纯SF_(6)气体的1.33倍。对126kV GIS用接地开关的绝缘结构进行了优化设计,优化的电场强度最大值较优化前下降了25.8%,大大提高了绝缘可靠性。特变电工自主研制的126kV SF_(6)/N_(2) GIS在机械工业高压电器产品质量检测中心顺利通过了绝缘、温升等整套型式试验验证,目前该126kV GIS可应用于国网公司新建环保GIS电站及现有SF_(6)在运电站改造。 Compared with pure SF_(6),SF_(6)/N_(2) gas mixture has the advantages of environmental protection,low liquefaction temperature,good insulation performance and economy.The study on the insulation performance of SF_(6)/N_(2) gas mixture shows that the pressure of SF_(6)/N_(2)(30%SF_(6))should be 1.33 times of that of pure SF_(6) in order to achieve the same breakdown strength.The insulation structure of grounding switch in 126kV GIS is optimized,the maximum electric field strength is 15.12%lower than that before optimization,which greatly improves the insulation reliability.The 126kV SF_(6)/N_(2) GIS independently developed by TBEA has successfully passed the complete set of type test verification such as insulation and temperature rise in the mechanical industry high-voltage electrical equipment product quality inspection center.At present,the 126kV GIS can be applied to the new environmental GIS power station and the existing SF_(6) power station improvement.
作者 王坤 龙腾 孟珍政 殷福煜 唐华超 孟维东 魏俊梅 WANG Kun;LONG Teng;MENG Zhen-zheng;YIN Fu-yu;TANG Hua-chao;MENG Wei-dong;WEI Jun-mei(TBEA Yunji High Voltage Switchgear Co.Ltd.,Hengyang 421099,China;TBEA Hengyang Transformer Co.Ltd.,Hengyang 421099,China)
出处 《电气开关》 2023年第3期48-51,共4页 Electric Switchgear
关键词 SF_(6)/N_(2) GIS 绝缘性能 环保 SF_(6)/N_(2) GIS insulation performance environmental protection
  • 相关文献

参考文献2

二级参考文献21

  • 1G.Schoeffner,T.Neumann.气体绝缘管道输电线和气体绝缘组合电器在电厂中的应用[J].电力建设,2004,25(6):4-7. 被引量:21
  • 2邱毓昌,冯允平,张鸣超.SF_6/N_2混合气体绝缘介质的研究[J].西安交通大学学报,1993,27(1):1-6. 被引量:18
  • 3Qiu Yuchang, Kufffel E.Comparisonof SF6/N2 and SF6/ CO2 Gas Mixtures as Alternative to SF6 Gas[J]. IEEE Trans onDEI,1999,6(6):892~895.
  • 4Christophorou L G, Olthoff J K, Van Brunt R J. Sulfur Hexafluoride and the ElectricPower Industry [J].IEEE Electrical Insulation Magazine,1997, 13(5): 20~24.
  • 5Qiu X. Q., Chalmers I D, Coventry P. A Study of Alternative Insulating Gases toSF6[J]. J.Phys.D:Appl. Phys.,1999,32: 2918~2922.
  • 6Singha S,Thomas M.J. Very Fast Transient Over- voltages in GIS with CompressedSF6-N2 Gas Mixtures.IEEE Trans. on DEI,2001,8(4):658~664.
  • 7Ueno H, Sakamoto N, Nakayama H. Anomalous Creeping Flashover Characteristics inN2/SF6 Mixed Gas under Single Pulse Voltage[J].IEEE Trans on DEI, 2001,8(2):195~202.
  • 8Biarra T B,Béroual A,Buret F et al.N2/SF6 Mixtures for High Voltage GasInsulated Line[C]. 1997,10th ISH.
  • 9Dissenter A, Finkel M, Grund A, Kynast E. Dielectric Properties of N2/SF6 Mixturesfor Use in GIS or GIL[C]. 1999,11th ISH.
  • 10Marsden H I, Dale S J, Hopkins M D, Eck III C R. High Voltage Performance of a GasInsulated Cable with N2 and N2/SF6 Mixture[C].1997, 10th ISH.

共引文献78

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部