热管与空调复合技术用于移动通信基站效果分析 被引量:2

Effect analysis of temperature control equipment for outdoor communication cabinet
原文传递
导出
摘要 针对河南移动通信基站机柜空调温控效果较差、能耗较高、柜内设备常发生高温报警等突出问题,提出采用热管与空调复合技术方案,开发了一体化产品样机,并对郑州地区基站机柜空调进行试点改造应用,实测结果表明:相对原机柜空调,热管与空调复合技术保证全年基站机柜温度在10℃~39℃之间,符合国家标准,柜内BBU(Building Base band Unit)设备无高温报警,基站全年PUE(Power Usage Effectiveness)由原来的1.7降为1.2,降低了29%,节能效果十分显著。 Aiming at the big problems of poor temperature-control effect,high energy consumption and high-temperature alarm often occurring in the equipment in Henan mobile communication base station,a composite technology scheme of heat pipe and air conditioner was proposed,and an integrated product prototype was developed.The experimental results show that compared with the original base station air conditioner,the composite technology can ensure that the temperature of the base station cabinet is between 10℃and 39℃throughout the year,which can meet the national standards.There is no high-temperature alarm for BBU(baseband processing unit of base station)equipment in the cabinet,and the PUE(Power Usage Effectiveness)of base station is reduced from 1.7 to 1.2,which is 29%lower,and the energy-saving effect is very remarkable.
作者 崔四齐 关斯泽 白静 杨涵斐 张毅 范惠芳 许闯 Cui Siqi;Guan Size;Bai Jing;Yang Hanfei;Zhang Yi;Fan Huifang;Xu Chuang(School of Energy&Environment,Zhongyuan University of Technology,Zhengzhou 450007,China)
出处 《低温与超导》 CAS 北大核心 2023年第5期85-89,共5页 Cryogenics and Superconductivity
基金 河南省科技攻关项目(202102310556) 河南省高等学校重点科研项目(20A480006)资助。
关键词 基站机柜 热管 空调 PUE Base station cabinet Heat pipe Air conditioner PUE
  • 相关文献

参考文献8

二级参考文献74

  • 1王前方.机房专用空调与舒适性空调区别[J].制冷与空调(四川),2004,18(3):54-56. 被引量:6
  • 2侯福平.通信机房空调系统节能技术探讨[J].电信技术,2006(6):20-21. 被引量:24
  • 3GB50174-2008.电子信息系统机房设计规范[S].北京:中国计划出版社,2008.
  • 4王永刚,张勤.利用热管技术降低机房能耗[C].厦门:节能减排——通信电源新技术论坛暨2011通信电源学术研讨会,2011:19 -25.
  • 5Code of conduct on data centres, energy efficiency-Version 2. O[ R]. European Commission, 2009.
  • 6Jonathan Koomey. Growth in data center electricity use 2005 to 2010 [ EB/OL]. (2011-08-01) [ 2014-10-28 ]. http: //www. analyticspress, com/datacenters, html.
  • 7Mitchell-Jackson J, Koomey J G, Blazek M, et al. Nation- al and regional implications of internet data center growth in the US [ J ]. Resources, Conservation and Recycling, 2002, 36(3) : 175-185.
  • 8李智.下一代通信机房及IDC数据中心能源成本战略[C]//第十届中国科协年会信息化与社会发展学术讨论会分会场论文集.北京:国防工业出版社,2008:458-462.
  • 9Zhang H, Shao S, Xu H, et al. Free cooling of data cen- ters: A review[ J]. Renewable and Sustainable Energy Re- views, 2014, 35: 171-182.
  • 10Han L, Shi W, Wang B, et al. Development of an inte- grated air conditioner with thermosyphon and the applica- tion in mobile phone base station[ J]. International Journal of Refrigeration, 2013, 36: 58-69.

共引文献95

同被引文献13

引证文献2

二级引证文献1

相关作者

内容加载中请稍等...

相关机构

内容加载中请稍等...

相关主题

内容加载中请稍等...

浏览历史

内容加载中请稍等...
;
使用帮助 返回顶部