全-半混合型柔性直流输电系统具有故障自清除能力,能在一定程度上解决因高压直流断路器技术滞后导致的柔性直流输电容量提升困难问题,是新能源发电大容量远距离输出的解决方案之一。但全-半混合型柔性直流输电对保护时间提出了更高要求,需要在更短时间内实现故障识别。该文基于能量观点分析了直流线路故障下桥臂功率特征,提出基于桥臂功率特征的全-半混合型柔性直流输电线路保护方法,能够在1 ms内识别直流线路故障,实现故障选极。最后,通过大量实时数字模拟(RTDS)实验验证了该方法的可靠性高、选择性好,且具有较强的耐过渡电阻能力和抗干扰能力。
The"Carbon-Neutral"goal is the main driving force to build a new power system with renewable energy.Due to the advantages of low loss and no commutation failure,the voltage source converter(VSC)transmission based on modular multilevel converter(MMC)has been widely used in large-scale renewable energy grid-connected power transmission.When the DC line faults,the fault current increase rapidly,causing irreversible damage to power electronic power devices and even paralysis of the transmission system.It brings a serious crisis to the safe operation of the power grid.Therefore,fast and selective identification of DC line faults is one of the key technologies to be solved urgently.The protection research of the VSC-HVDC transmission system based on full-half hybrid sub-modular structure is of great significance to the large capacity transmission of renewable energy.Firstly,the bridge arm power calculation circuit is equivalent when the DC line is faulted,and the change characteristics of the bridge arm power under the DC line fault are analyzed.When the DC line faults,the bridge arm power increases.Then,the bridge arm power under DC fault is numerically analyzed,and the causes of errors are analyzed in detail.Finally,based on the power characteristics of the bridge arm,the protection scheme of the DC transmission line is proposed,the set-up element,the identification element of internal and external fault,and the faulty poles detection element are constructed,and the complete protection flow chart is given.A double-ended true bipolar full-half hybrid MMC-HVDC transmission system is built on the RTDS platform.The system adopts the overhead line,the transmission distance is 500 km,and the transmission line adopts the frequency-variable model,and the transmission capacity is 1280 MW,the fault occurrence time is 3 s,the simulation step is 2μs,the sampling step is 100μs,the sampling frequency is 10 kHz,and the protection interruption time is 0.7 ms.Firstly,the protection effect under different fault types is verified.When an AC fault occurs,,it is judged as an external fault.When a DC fault occurs,,it is judged as an internal fault.When a positive fault occurs,,when a negative fault occurs,.When a pole-to-pole fault occurs,,which satisfies the pole detection criterion.The protection method proposed in this paper can correctly identify the fault and select the faulty poles under different fault types.Then the protection effect under different transition resistances and distance is verified.When the transition resistances are 0.01Ω,100Ω,300Ωand 500Ω,the fault distance are 20 km,120 km,300 km and 480 km,respectively.When a positive fault,a negative fault,and a pole-to-pole fault occurs,the internal/external fault identification criteria and pole selection criterion is satisfied.Furthermore,the anti-interference ability of the protection scheme is verified.And compared with the existing protection methods,the protection scheme has strong ability to response to the high transition resistance and noise interference.Based on the energy point,this paper analyzes the bridge arm power characteristics of the VSC-HVDC transmission system under DC line faults,proposes a protection scheme of this VSC-HVDC transmission system based on the bridge arm power characteristics.The conclusion can be drawn as follows:(1)When a DC line faults,the bridge arm capacitor discharges to the fault point on the DC side,and the fault current direction is the same as the current direction of the original system.Therefore,when the DC line faults,the bridge arm power increases.(2)The protection scheme is constructed by using the bridge arm power characteristics.The scheme is simple,and it can reliably identify the DC line fault.(3)Compared with the traditional time domain and frequency domain method,it is verified that the protection scheme proposed is highly reliable,selective,and sensitive,has strong ability to response to the high transition resistance and noise interference.
作者
雷顺广
束洪春
李志民
Lei Shunguang;Shu Hongchun;Li Zhimin(School of Electrical Engineering and Automation Harbin Institute of Technology,Harbin 150001 China;Faculty of Electric Power Engineering Kunming University of Science and Technology,Kunming 650051 China)
出处
《电工技术学报》
EI
CSCD
北大核心
2023年第13期3563-3575,共13页
Transactions of China Electrotechnical Society
基金
国家自然科学基金重点项目(52037003)
云南省重大科技专项计划项目(202002AF080001)资助。
关键词
全-半混合型
柔性直流输电
等效电路
桥臂功率特性
直流线路保护
Full-half hybrid
voltage source converter based high voltage direct current(VSC-HVDC)
equivalent circuit
bridge arm power characteristics
DC line protection